BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B342877
Premises: 487 KEAP STREET BROOKLYN BIN: 3062531     Block: 2371   Lot: 34
   
Application Completed and Certified

Filed: 487 KEAP ST Census Tract:   513 Health Area:  0700
CELLAR, 1-6 & ROOF Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    320044607
DOB Cross Street(s):   AINSLIE STREET,    UNION AVENUE
Status:   C - JOB IS SIGNED OFF 03/22/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/25/2011 1:55 PM
Application Entered:   09/25/2011 Job Start Date:   09/26/2011
Last Change:   03/22/2013 Job End Date:   09/25/2014
Appointment Status:   
Last Inspection By:   BEST, J       On     02/26/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011988 Licensee Name: ZVI SARAFRAZ
Firm: 003730 Firm Name: HORSEPOWER ELECTRIC.&
Firm Phone: 718-437-6937  Firm Address: 4101 1ST AVENUE MAINTENANCE, CORP BROOKLYN NY 11232 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $3,993.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   E - EMERGENCY LIGHTING LOCAL LAW 16/84 L - FIRE ALARM LOCAL LAW #5
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   
Owner / Occup: MAYER CHETRIT
Owner Business Name: 487 KEAP STREET LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  1  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  51  
C. 3 Phase Up to 225 AMPS  4  
D. 3 Phase Over 225 AMPS  1  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    31  14  79  64     
001    33  157  50  160         
002    34  168  20  72  147         
003    34  169  20  73  149         
004    34  168  20  72  147         
005    34  168  20  72  147         
006    28  138  17  58  124         
ROF    20  32  18     
Buildings Total 209  1006  102  413  973     82     26      
Total Units : 2811 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 51 #4-Wire 1 #10-Wire 1
Existing Meters 0 + New Meters 53 - Removed Meters 0 = Total Meters 53

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/25/2011 Notice: 1 - FIRST NOTICE 02/11/2013
Power Issued: 09/25/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WE ARE FILING THIS APLICATION AS PER THE NYC2007 ELECTRICALCODE.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B342877
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/04/2013 02/11/2013 CJE A E (90) (4) Y
INSPECTION COMMENTS: N
 
(2) 02/26/2013 03/04/2013 JSB C R E (180) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B342877
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
NO AFCI PROTECTION FOR AC THROUGHOUT BUILDING IN BEDROOMS ART 210.12
RSLV 02/04/2013 02/04/2013 02/26/2013
 
002 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
SAME CIRCUITS NOT GROUPED 300.3 (2)
RSLV 02/04/2013 02/04/2013 02/26/2013
 
003 (315) CONDUCTORS NOT PROPERLY IDENTIFIED
CONDUCTORS NOT IDENTIFIED 200.6
RSLV 02/04/2013 02/04/2013 02/26/2013
 
004 (999) OTHER
MULTIWIRE BRANCH CIRCUIT MEANS OF DISCONNECT NOT SIMULTANEOUSLY ART210.4
RSLV 02/04/2013 02/04/2013 02/26/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back