Electrical Application Details for App #: B342736
Premises: 30 CLAVER PLACE BROOKLYN BIN: 3057297     Block: 1994   Lot: 37
   
Application Completed and Certified

Filed: 30 CLAVER PL Census Tract:   227 Health Area:  1300
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11238 Community Board:   303
DOB Cross Street(s):   JEFFERSON AVENUE,    FULTON STREET
Status:   C - JOB IS SIGNED OFF 09/18/2013 Balance Paid By Owner
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/20/2011 5:40 PM
Application Entered:   09/20/2011 Job Start Date:   09/20/2011
Last Change:   09/18/2013 Job End Date:   09/20/2011
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     08/28/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009252 Licensee Name: MORRIS HELLER
Firm: 000647 Firm Name: HELLER ELECTRIC CO., INC.
Firm Phone: 718-871-0800  Firm Address: 620 CONEY ISLAND AVE BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $483.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: WAGSHAL ZALMEN
Owner Business Name: BH MANAGEMENT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400 AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  9  3/3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  10  12/20
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001  14             
001                   
001  14             
002                   
002  12  20             
003                   
003                   
004  14  20             
004  14  20             
Buildings Total 56  88    34       45           
Total Units : 223 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 10 #4-Wire 0 #10-Wire 0
Existing Meters 9 + New Meters 10 - Removed Meters 9 = Total Meters 10

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/20/2011 Notice: 1 - FIRST NOTICE 04/12/2012
Power Issued: 09/20/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B342736
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/01/2012 02/06/2012 PGR P (50) (0) Y
INSPECTION COMMENTS: THIS JOB ASSIGNED TO JMZ ON 02/14
 
(2) 02/14/2012 02/22/2012 JMZ N (60) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(3) 04/05/2012 04/12/2012 DEX V E (60) (5) Y
INSPECTION COMMENTS: GOT ACCESS TO APTS. 2R, 1R, 3R AND 4R ONLY
 
(4) 05/08/2012 05/10/2012 PGR N (20) (0) Y
INSPECTION COMMENTS: N
 
(5) 08/09/2013 08/12/2013 CCH N (60) (0) Y
INSPECTION COMMENTS: NO ACCESS
 
(6) 08/28/2013 09/04/2013 CJH C R E (35) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B342736
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ROOF A/C/HEATING UNITS NO GFCI OUTLET INSTALLED 210.63
RSLV 04/05/2012 04/05/2012 08/28/2013
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
THROUGHOUT PANELS BONDED AFTER SERVICE SWITCHES APTS 3L,2L,1R AND 1F
RSLV 04/05/2012 04/05/2012 08/28/2013
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF A/C/HEATING EQUIPMENT CONNECTOR FOR ALL FITTINGS ON UNIT ISLOOSE
RSLV 04/05/2012 04/05/2012 08/28/2013
 
004 (999) OTHER
THROUGHOUT SPLICE BOXES BURIED FOR OLD APARTMENTS NO WIRES THROUGH-OUT 314.00
RSLV 04/05/2012 04/05/2012 08/28/2013
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
APT#4L FEEDER CONDUCTOR FOR PANEL NOT INSTALLED IN PANEL
RSLV 04/05/2012 04/05/2012 08/28/2013