Premises: 471 FULTON STREET BROOKLYN BIN: 3000404     Block: 152   Lot: 6
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 151 LAWRENCE ST Census Tract:   11 Health Area:  2300
BASEMENT TO ROOF Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   WILLOUGHBY STREET,    FULTON STREET
Status:   C - JOB IS SIGNED OFF 10/20/2016
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/18/2011 3:30 PM
Application Entered:   08/18/2011 Job Start Date:   08/18/2011
Last Change:   10/20/2016 Job End Date:   08/18/2012
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     10/20/2016      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011747 Licensee Name: IGOR BRON
Firm: 003605 Firm Name: E ELEC'L CONTR'G LLC
Firm Phone: 718-336-0276  Firm Address: 2355 MCDONALD AVENUE BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
Total Fee:  $165.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ELI KRAIEM
Owner Business Name: FULTON REALTY VENTURE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  1  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF                       
Buildings Total                       
Total Units : 1 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/25/2012 Notice: 1 - FIRST NOTICE 07/20/2016
Power Issued: 05/25/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B341744
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/06/2012 02/15/2012 DEX N (0) (0) Y
INSPECTION COMMENTS: N
 
(2) 05/23/2012 05/25/2012 PGR V E (55) (5) Y
INSPECTION COMMENTS: NOT FINAL INSPECTION DIDNT INSPECT ELEVATOR
 
(3) 10/17/2012 10/19/2012 HRB J Y (25) (0) Y
INSPECTION COMMENTS: N
 
(4) 07/19/2016 07/20/2016 NRS V R (79) (2)
INSPECTION COMMENTS: CONTRACTOR ONLY REPLACED #4 ELEVATOR (NYC ELEV ID# 3P7925) MAIN SWITCH, CONDUIT TO CONTROLLER & FEEDER TO BETWEEN SWITCH & CONTROLLER IN MOTOR ROOM. REST OF INSTALLATION BY OTHER COMPANY IN 2011. (3) OBJECTIONS NOT RELATED TO WORK REMOVED.
 
(5) 10/20/2016 10/20/2016 HRB C R (40) (0)
INSPECTION COMMENTS: PASSED

OBJECTION FOR APPLICATION #: B341744
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
DISCONNECT SWITCH
RSLV 05/23/2012 05/23/2012 10/17/2012
 
002 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
(ALL FLOORS) BY ELEVATOR CONTROLLER PANEL GFCI OUTLET
RSLV 05/23/2012 10/17/2012 07/19/2016
 
003 ( 19) DEFECTIVE WIRING IS IN USE
(ALL FLOORS) BY ELEVATOR CONTROLLER PANEL GFCI OUTLETS
RSLV 05/23/2012 10/17/2012 07/19/2016
 
004 (181) DISCONNECTING MEANS IS IMPROPER/NOT PROVIDED
(ALL FLOORS) FOR CAB LIGHT
RSLV 05/23/2012 10/17/2012 07/19/2016
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
(ALL FLOORS) 100A SWITCH NOT LABEL FOR NEW ELEVATOR SWITCH
RSLV 05/23/2012 10/17/2012 07/19/2016
 
006 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
(ROOF) BETWEEN 100AMP MAIN & CONTROLLER
RSLV 07/19/2016 07/19/2016 10/20/2016
 
007 (999) OTHER
(ROOF) FEEDER TO CONTROLLER NOT SIZED AS PER 620.13(B)
RSLV 07/19/2016 07/19/2016 10/20/2016