BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B340836
Premises: 1045 64 STREET BROOKLYN BIN: 3141758     Block: 5737   Lot: 58
   
Application Completed and Certified

Filed: 1045 64 ST Census Tract:   212 Health Area:  8020
BASMENT Admin Area:   B - BROOKLYN Inspection Area:   M
BROOKLYN, NY 11219 Community Board:   310
DOB Cross Street(s):    10 AVENUE,    11 AVENUE
Status:   C - JOB IS SIGNED OFF 09/15/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  07/20/2011 5:03 PM
Application Entered:   07/20/2011 Job Start Date:   07/22/2011
Last Change:   09/15/2014 Job End Date:   06/15/2012
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     08/13/2014      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009747 Licensee Name: MELVYN ZWEBNER
Firm: 002640 Firm Name: ILLUMINOUS ELECTRIC CORP.
Firm Phone: 718-431-1605  Firm Address: 1425 37TH STREET BROOKLYN NY 11218 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $355.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: TRUST 1045 64ST
Owner Business Name: 1045 64ST TRUST
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  13  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 13 #4-Wire 0 #10-Wire 0
Existing Meters 13 + New Meters 13 - Removed Meters 13 = Total Meters 13

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/20/2011 Notice: 1 - FIRST NOTICE 07/29/2014
Power Issued: 07/20/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B340836
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/08/2014 01/13/2014 CJH N (30) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(2) 01/31/2014 02/04/2014 RJO J E (30) (0) Y
INSPECTION COMMENTS: N
 
(3) 04/01/2014 04/08/2014 EBA A E (30) (2) Y
INSPECTION COMMENTS: N
 
(4) 07/22/2014 07/29/2014 CJE A Y E (40) (2) Y
INSPECTION COMMENTS: N
 
(5) 08/13/2014 08/19/2014 CJE C R E (20) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B340836
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
NO WATER METER JUMPER 250.53.D.1
RSLV 04/01/2014 04/01/2014 07/22/2014
 
002 (999) OTHER
NO ILLUMINATION AT S/S 110.26.D
RSLV 04/01/2014 07/22/2014 08/13/2014
 
003 (220) DOUBLE LUGGING IN SERVICE SWITCH
WATER MAIN JUMPER + SERVICE GROUND ON SAME LUG. ART 110.14(A)
RSLV 07/22/2014 07/22/2014 08/13/2014
 
004 ( 19) DEFECTIVE WIRING IS IN USE
LIGHT HANGING BY CONDUCTORS FROM CEILING AMEND 110.2(A)
RSLV 07/22/2014 07/22/2014 08/13/2014



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order