BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B339573
Premises: 103 NORTH 3 STREET BROOKLYN BIN: 3335727     Block: 2350   Lot: 26
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 103 N 3 ST Census Tract:   555 Health Area:  0400
1 FL Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11211 Community Board:   301
DOB Cross Street(s):   WYTHE AVENUE,    BERRY STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/10/2011 10:48 AM
Application Entered:   06/10/2011 Job Start Date:   06/10/2011
Last Change:   08/22/2025 Job End Date:   04/10/2012
Appointment Status:   
Last Inspection By:   JEFFERSON, CHARLES       On     01/29/2013      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011538 Licensee Name: NICHOLAS BLASONE
Firm: 003044 Firm Name: NEW CENTURY ELEC'L CONTR
Firm Phone: 718-441-7123  Firm Address: 105-15 JAMAICA AVE INC. QUEENS NY 11418 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $370.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (6  Stores, 20 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: OLGA SOSA
Owner Business Name: BERRY ENTERPRISES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1-200A MB COMBO PANEL
C. 201 Up to 600 AMPS  1  1 600A S S
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1 SET # 3/0
D. Over 250 MCM  2  2 SETS # 350 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 1 #10-Wire 0
Existing Meters 0 + New Meters 1 - Removed Meters 0 = Total Meters 1

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 06/10/2011 Notice: 1 - FIRST NOTICE 02/20/2013
Power Issued: 06/10/2011 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B339573
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/19/2012 06/27/2012 DEX P (35) (0) Y
INSPECTION COMMENTS: CONTRACTOR NOT PRESENT JOB - PROBLEM JOB - POWER FEEDING INTO TWO DIFFERENT BUILDINGS CONTRACTOR NEED TO EXPLAIN JOB
 
(2) 10/31/2012 11/05/2012 CJE N (25) (0) Y
INSPECTION COMMENTS: CONTRACTOR HAD NO ONE
 
(3) 11/27/2012 12/01/2012 CJE N (20) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(4) 01/29/2013 02/20/2013 CJE A E (45) (2) Y
INSPECTION COMMENTS: SERVICE IS IN 103 METERS IN 105 SERVICE WAS FOR STORE 109

OBJECTION FOR APPLICATION #: B339573
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
600A SECURE NEUTRAL NOT BONDED GROUNDED ART 250.94 (C)
OPEN 01/29/2013 01/29/2013
 
002 (999) OTHER
POWER DITRIBUTION BLOCK IN WIREWAY NOT COVERED ART 376.56 (B) (4)
OPEN 01/29/2013 01/29/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Marquee Query  |  Electrical Inspection Work Order  |  Back