BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B339558
Premises: 6302 4 AVENUE BROOKLYN BIN: 3144053     Block: 5808   Lot: 34
   
Application Completed and Certified

Filed: 376 63 ST Census Tract:   72 Health Area:  7600
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   S
BROOKLYN, NY 11220 Community Board:   307
DOB Cross Street(s):   GOWANUS EXPRESSWAY EB EXIT 21,    4 AVENUE
Status:   C - JOB IS SIGNED OFF 01/29/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/09/2011 9:35 PM
Application Entered:   06/09/2011 Job Start Date:   06/13/2011
Last Change:   01/29/2013 Job End Date:   09/20/2011
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     01/23/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011217 Licensee Name: RICHARD MARTINEZ
Firm: 002617 Firm Name: A #1 UNIVERSAL ELEC'L INC
Firm Phone: 718-768-0360  Firm Address: 1718 8TH AVENUE BROOKLYN NY 11215 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $235.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (2  Stores, 21 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: REALTY DELLERIMAR
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400A MP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  PLP BASEMENT PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 23 #4-Wire 1 #10-Wire 0
Existing Meters 24 + New Meters 24 - Removed Meters 24 = Total Meters 24

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/09/2011 Notice: 1 - FIRST NOTICE 04/16/2012
Power Issued: 06/09/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLATION OF 400 AMP SERVICE UPGRADE / PICK UP EXISTING LOADS IN BASEMENT FOR 21 APT 2 STORES AND 1PLP.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B339558
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/14/2012 04/16/2012 HRB V D (60) (4) Y
INSPECTION COMMENTS: N
 
(2) 01/23/2013 01/29/2013 HRB C R E (20) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B339558
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
#2 FUSED AT 150 AMPS
RSLV 04/14/2012 04/14/2012 01/23/2013
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
RACEWAY NOT BONDED (TROFF)
RSLV 04/14/2012 04/14/2012 01/23/2013
 
003 ( 49) TEMPORARY OPEN WIRING INSTALLED IS NOT PROPERLY SUPPORTED
TEMP WIRES IN CONTACT WITH BUILDING
RSLV 04/14/2012 04/14/2012 01/23/2013
 
004 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
150 AMP SERVICE SWITCH NOT BONDED
RSLV 04/14/2012 04/14/2012 01/23/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back