BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B337992
Premises: 964 CONEY ISLAND AVENUE BROOKLYN BIN: 3127968     Block: 5425   Lot: 31
   
Application Completed and Certified

Filed: 964 CONEY ISLAND AV Census Tract:   482 Health Area:  7000
GROUND FLOOR Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11230 Community Board:   314
DOB Cross Street(s):   WEBSTER AVENUE,    NEWKIRK AVENUE
Status:   C - JOB IS SIGNED OFF 05/30/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/21/2011 6:41 PM
Application Entered:   04/21/2011 Job Start Date:   04/27/2011
Last Change:   05/30/2012 Job End Date:   10/23/2011
Appointment Status:   
Last Inspection By:   COHN, MARTIN       On     05/09/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009840 Licensee Name: MAURICE SITRUK
Firm: 000536 Firm Name: FOSTER ELEC'L SVC., INC.
Firm Phone: 718-438-9100  Firm Address: 1325 FOSTER AVENUE BROOKLYN NY 11230 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $74.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   Z - Commercial/Residential (1  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ALI ABID
Owner Business Name: JANAAN PIKKITA HOUSE
Authorized Representative:  ALI ABID
Relationship To Owner:   STORE OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1   3# 3
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1   12/24
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    15               
Buildings Total 15                  
Total Units : 28 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/15/2012 Notice: C - CALL TO OFFICE 05/01/2012
Power Issued: 05/15/2012 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  WIRING FOR STORE AND RISER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B337992
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 07/18/2011 07/25/2011 JMZ A (10) (1) Y
INSPECTION COMMENTS: N
 
(2) 12/30/2011 01/04/2012 JMZ H X (15) (0) Y
INSPECTION COMMENTS: N
 
(3) 03/08/2012 03/13/2012 PAT A R (30) (2) Y
INSPECTION COMMENTS: N
 
(4) 04/27/2012 05/01/2012 JMZ H X (15) (0) Y
INSPECTION COMMENTS: RECEPTACLE REVERSE POLARITY
 
(5) 05/09/2012 05/15/2012 MC2 C R E (15) (0) Y
INSPECTION COMMENTS: VIOLATION REMOVED

OBJECTION FOR APPLICATION #: B337992
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
AFCI USED AS GFI KITCHEN CIRCUIT
RSLV 07/18/2011 12/30/2011 03/08/2012
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
GROUND FLOOR - PANEL #12 AWG PROTECTED BY 30AMPS BREAKER
RSLV 03/08/2012 04/27/2012 05/09/2012
 
003 ( 53) GFCI HAS NOT BEEN PROVIDED
GROUND FLOOR - RECEPTACLE NOT PROTECTED BY GFCI IN KITCHEN AREA
RSLV 03/08/2012 04/27/2012 05/09/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Pre-BIS PA CO Query By Bin  |  Electrical Inspection Work Order  |  Back