| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
1X100AMPS |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
1SET |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
2 |
2X20-1 CIR.BRKR. PANEL |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY WATER GROUND NOT CONTINOUS 250.24 (C) |
RSLV |
02/25/2013 |
02/25/2013 |
01/29/2013 |
| |
| 002 |
(242) |
SERVICE ENTRANCE RACEWAY IS NOT SEALED CIRCUITS NOT GROUPED ART 300.3 (B) IN ALL PANELS |
RSLV |
02/25/2013 |
02/25/2013 |
01/29/2013 |
| |
| 003 |
( 37) |
MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED BOILER DIS SW NOT ON OUTSIDE ROOM |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED BOILER ROOM OUTLET NOT GFCI |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |
| |
| 005 |
(999) |
OTHER A KITCHEN ISLAND NO OUTLET INSTALLED 210.52 C.2 |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |
| |
| 006 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE CLOSET LIGHT NO GLOBE |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |
| |
| 007 |
(999) |
OTHER B BOILER ROOM LIGHT NO DANGER PROOF COVER 410.4 |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |
| |
| 008 |
(999) |
OTHER C REAR LIGHT NOT SUITABLE FOR WET LOCATION 410.4 |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |
| |
| 009 |
( 42) |
BUSHINGS ARE MISSING OR LOOSE NO RED BUSHING ON BOX CABLE IN PANEL |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |
| |
| 010 |
(999) |
OTHER D NO ARC FAULT FOR ALL BEDROOMS 210.12 |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |
| |
| 011 |
( 35) |
APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS NO AC OUTLET NOT IN ALL ROOMS |
RSLV |
01/29/2013 |
01/29/2013 |
03/26/2013 |