| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
100A, 3 PH |
| B. 101 Up to 200 AMPS |
2 |
200A 3 PH |
| C. 201 Up to 600 AMPS |
2 |
2600 + 1 |
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
18 |
#2 |
| B. Over #2 to 1/0 |
1 |
1/0 |
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
5 |
1X3/0, 4X350 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
17 |
|
| C. 3 Phase Up to 225 AMPS |
2 |
|
| D. 3 Phase Over 225 AMPS |
3 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
1 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER EQUIPMENT NOT PROPERLY BONDED PARALLEL FEEDERS |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 002 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER EQUIPMENT NOT PROPERLY BONDED. 250.92(A) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 003 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY NEUTRAL NOT GROUNDED 250.24(C) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 004 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE NEUTRAL NOT BONDED. 250.28 |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 005 |
(129) |
SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE NEUTRAL NOT BONDED. 250.28 |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 006 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH DOUBLE LUGGING OF BONDING JUMPER 110.14(A) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 007 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH DOUBLE LUGGING OF BONDING JUMPER 110.14(A) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 008 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY NEUTRAL NOT GROUNDED. 250.24(C) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 009 |
(135) |
DEFECTIVE GROUND ROD IS IN USE GROUND ROD + CLAMP IN CEMENT. 250.52(A) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 010 |
( 53) |
GFCI HAS NOT BEEN PROVIDED COMPACTOR ROOM RECEPTACLE NOT GFCI |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 011 |
( 53) |
GFCI HAS NOT BEEN PROVIDED GARGE RECEPTACLE NOT GFCI |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 012 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER KITCHEN COUNTER TOP RECEPTACLE MISSING 210.12(B) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 013 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED A/C RECEPTACLES IN BEDROOMS NOT AFCI 210.12(B) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 014 |
(311) |
FIXTURE NOT APPROVED FOR DAMP/WET LOCATION BATHROOM FIXTURES SUITABLE FOR DRY LOCATIONS ONLY. 410.10(D) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 015 |
(284) |
NO OUTLET FOR KITCHEN ISLAND 4TH FL APT NO ISLAND/PENINSULA OUTLETS 210.52(C2) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 016 |
(282) |
MINIMUM NUMBER OF SMALL APPLIANCE CIRCUITS 4F + 4A ONE COUNTER TOP RECEPTACLE + CIRCUIT. 210.52(B1) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 017 |
(236) |
OUTSIDE A/C DISCONNECT NOT ACCESSIBLE A/C DISCONNECT MOUNTED BEHIND UNITS 440.14 |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 018 |
(220) |
DOUBLE LUGGING IN SERVICE SWITCH DISCONNECT SWITCHS DOUBLE LUGGIN OF GROUND. 110.14(A) |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 019 |
(273) |
GROUND CLAMP NOT ACCESSIBLE GROUND CLAMP IN CEMENT 250.68 |
RSLV |
01/21/2014 |
01/21/2014 |
03/07/2014 |
| |
| 020 |
(999) |
OTHER BSMT TROUGH LINE AND LOAD IN THE SAME RACEWAY 230.7 |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 021 |
(999) |
OTHER BSMT 600 AMP PANEL NEUTRAL AND PHASE COND NOT GROUPED 300.20A |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 022 |
(999) |
OTHER BSMT SVC ENT RACEWAYS NOT BONDED TROUGH 250.92A |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 023 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE BSMT ROOF PANEL FEEDER OVER FUSE |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 024 |
(999) |
OTHER BSMT SVC GND RACEWAY NOT CONTINOUS 250.64C |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 025 |
(999) |
OTHER BSMT COMPAC RM DISCONN NEUTRAL BONDED 250.25 A5 |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 026 |
(999) |
OTHER APTS ALL PENNSUILA GFCI NOT PROVIDED 210.52 C3 |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 027 |
(999) |
OTHER ALL APTS BEDROOM LIGHTS NOT AFCI PROTECTED 210.12B |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 028 |
(999) |
OTHER 1ST MC CABLE GNDS NOT BONDED TO BOXES 250.118 |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |
| |
| 029 |
(999) |
OTHER BSMT TROUGH BATH PARALLEL COND NOT TAP 310.4 |
RSLV |
03/07/2014 |
03/07/2014 |
03/24/2014 |