BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B337156
Premises: 180 SCHOLES STREET BROOKLYN BIN: 3396894     Block: 3044   Lot: 16
   
Application Completed and Certified

Filed: 180 SCHOLES ST Census Tract:   4930 Health Area:  0800
ENTIRE BUILDING Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11206 Community Board:   301
Related Job Number:    302185828
DOB Cross Street(s):   GRAHAM AVENUE,    HUMBOLDT STREET
Status:   C - JOB IS SIGNED OFF 04/23/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/28/2011 11:42 AM
Application Entered:   03/28/2011 Job Start Date:   03/31/2011
Last Change:   04/23/2012 Job End Date:   02/01/2012
Appointment Status:   
Last Inspection By:   MOSES, FITZROY       On     03/02/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012302 Licensee Name: MAYER WEBER
Firm: 004070 Firm Name: METRO ELEC'L CONTRS, INC
Firm Phone: 718-439-7466  Firm Address: 218 HAMILTON AVENUNE BROOKLYN NY 11231 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $2,121.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: HI TOWER CONST
Authorized Representative:  SHEA KATZ
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  34  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  5  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  34  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    50  25    50  50             
001    50  100    50  50             
002    50  100    50  50             
003    50  100    50  50             
004    50  100    50  50             
ROF          34  70         
Buildings Total 255  425    250  255     70           
Total Units : 1255 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 34 #4-Wire 0 #10-Wire 1
Existing Meters 35 + New Meters 35 - Removed Meters 35 = Total Meters 35

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/28/2011 Notice: 1 - FIRST NOTICE 01/09/2012
Power Issued: 03/28/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B337156
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/31/2011 09/07/2011 DEX V E (90) (6) Y
INSPECTION COMMENTS: NO POWER IN BUILDING
 
(2) 01/04/2012 01/09/2012 FMO V R E (120) (4) Y
INSPECTION COMMENTS: N
 
(3) 03/02/2012 03/05/2012 FMO C R E (5) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B337156
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 25) ARMORED CABLES ARE NOT PROPERLY TERMINATED
THROUGHOUT MISSING LIGHTS
RSLV 08/31/2011 08/31/2011 01/04/2012
 
002 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
HANGING WIRES THROUGHOUT
RSLV 08/31/2011 08/31/2011 01/04/2012
 
003 (999) OTHER
GARAGE OUTLETS NOT GFI PROTECTED (210.8A2)
RSLV 08/31/2011 08/31/2011 01/04/2012
 
004 (999) OTHER
SPLICED BOX COVERED FOR A/C UNITS ON ROOF IN APARTMENT AND GARAGEAREA
RSLV 08/31/2011 08/31/2011 01/04/2012
 
005 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
THROUGHOUT NO DIRECTORY FOR PANELS THROUGHOUT
RSLV 08/31/2011 08/31/2011 01/04/2012
 
006 ( 29) OUTLET BOXES ARE NOT COVERED
THROUGHOUT MISSING OUTLETS AND SWITCH PLATES
RSLV 08/31/2011 08/31/2011 01/04/2012
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
SERVICE SWITCHES NOT PROPERLY GROUNDED
RSLV 01/04/2012 01/04/2012 03/02/2012
 
008 (999) OTHER
OUTLETS THROUGHOUT OVER 12 OVER HANG
RSLV 01/04/2012 01/04/2012 03/02/2012
 
009 ( 53) GFCI HAS NOT BEEN PROVIDED
GARAGE NOT PROVIDED WITH GFCI OUTLETS
RSLV 01/04/2012 01/04/2012 03/02/2012
 
010 ( 29) OUTLET BOXES ARE NOT COVERED
OUTLETS ON COUNTER TOP IN APT 4D AND 3E NOT ACCESSIBLE
RSLV 01/04/2012 01/04/2012 03/02/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order