BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B336753
Premises: 190 PLYMOUTH STREET BROOKLYN BIN: 3000037     Block: 31   Lot: 14
   
Application Completed and Certified

Filed: 205 WATER ST Census Tract:   2100 Health Area:  1000
LOBBY Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Related Job Number:    320107923
DOB Cross Street(s):   JAY STREET,    BRIDGE STREET
Status:   C - JOB IS SIGNED OFF 12/04/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/14/2011 3:37 PM
Application Entered:   03/14/2011 Job Start Date:   03/14/2011
Last Change:   12/04/2012 Job End Date:   07/02/2012
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     11/29/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012320 Licensee Name: RICHARD F FEIL
Firm: 003215 Firm Name: QUEST ELECTRIC CORP.
Firm Phone: 718-885-3367  Firm Address: 2362 WESTCHESTER AVENUE BRONX NY 10462 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
6 - GENERAL WIRING
8 - BOILER/BURNER WIRING
Total Fee:  $5,040.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   REQUIRED
Advisory Board Categories:      K - 1000 KVA SERVICE                            
Advisory Board Approval # / Submittal #:   50449
Owner / Occup: PETER MONTE
Owner Business Name: TOLL BROTHERS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  3  
E. Over 1200 AMPS  1  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  67  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  10  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  67  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  5  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    47  25    10               
001    45  10    15               
002    70  250    108               
003    70  250  11  108               
004    70  250  11  108               
005    70  250  11  108               
006    70  250  11  108               
007    70  250  11  108               
008    70  250  11  108  582             
Buildings Total 582  1785  66  781  582                
Total Units : 3796 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 67 #4-Wire 0 #10-Wire 1
Existing Meters 0 + New Meters 67 - Removed Meters 0 = Total Meters 67

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/14/2011 Notice: C - CALL TO OFFICE 11/19/2012
Power Issued: 03/14/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B336753
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/04/2012 05/25/2012 NI1 A B (240) (15) Y
INSPECTION COMMENTS: N
 
(2) 06/19/2012 06/26/2012 PGR A Y E (60) (2) Y
INSPECTION COMMENTS: N
 
(3) 09/18/2012 09/21/2012 HMC V R E (70) (3) Y
INSPECTION COMMENTS: N
 
(4) 11/19/2012 11/19/2012 HMC H X E (40) (0) Y
INSPECTION COMMENTS: N
 
(5) 11/27/2012 11/29/2012 HMC C R E (30) (0) Y
INSPECTION COMMENTS: SEE APPL B357007 FOR ROOF TERRACE VIOLATION
 
(6) 11/29/2012 11/29/2012 HMC C E (30) (0) Y
INSPECTION COMMENTS: SEE B357007

OBJECTION FOR APPLICATION #: B336753
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
FP AND FC - ALL
RSLV 05/04/2012 05/04/2012 06/19/2012
 
002 (999) OTHER
(A) SER.RM.FP - LINE AND LOAD ARE IN THE SAME ENCLOSURE WITH OTHERLOADS (695.3.A.1)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
003 (999) OTHER
(B) SER. RM. FP - FP SER ENT IS IN THE SAME ENCLOSURE WITH OTHERLOADS (695.3.A.1)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
004 (999) OTHER
(C) SERVICE SWITCH - GROUND RACEWAY IS NOT CONTINUOUS (250.64.E)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
005 (999) OTHER
(D) SERVICE SUBFEEDERS NOT DERATED (TAB. 310.15.B.2.A)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
006 (999) OTHER
(E) SERVICE ROOM - SERVCE ENTRANCE IS NOT 125% (695.6.C.(2)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
007 (999) OTHER
(F) SERVICE ROOM - DISCONNECT IS NOT WITHIN 25FT OF TAP (240.21.B2(2)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
008 (999) OTHER
(G) NEUTRAL BAR IS NOT BONDED AFTER SERVICE SWITCH (250.24(A)(5)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
009 (999) OTHER
(H)GREENFIELD IS NOT GROUNDED (250.118(6)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
010 (999) OTHER
(I)ENTIRE BUILDING - CONDUCTORS 4 AND LARGER NO BUSHING (300.4 F)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
011 (999) OTHER
(J) NO ADVISORY BOARD APPROVAL (110.2.B AMENDMENT)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
012 (999) OTHER
(K) ENTIRE BUILDING LIGHTS ARE NOT AFCI (210.12B)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
013 (999) OTHER
(L) ENTIRE BUILDING - BALCONY OUTLETS ARE NOT ON GFCI (210.8)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
014 (999) OTHER
(M) ENTIRE BUILDING - SMOKE DETECTORS ARE NOT AFCI (210.12B)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
015 (999) OTHER
FP RM -FP WIRING IS NOT IN RIGID RACEWAY (695.6D)
RSLV 05/04/2012 06/19/2012 09/18/2012
 
016 (105) TYPE EMT USED UNDERGROUND OR IN WET LOCATION
THROUGHOUT FOR LIGHT OUTLET A/C UNIT
RSLV 06/19/2012 06/19/2012 09/18/2012
 
017 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
NM CABLE USED FOR LIGHT OUTLET THROUGHOUT ROOF
RSLV 06/19/2012 06/19/2012 09/18/2012
 
018 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BSMT GROUND CONDUCTOR NOT TO LINE SIDE OF SERV SW
RSLV 09/18/2012 11/19/2012 11/27/2012
 
019 (105) TYPE EMT USED UNDERGROUND OR IN WET LOCATION
ROOF TERRACE OF PENT HOUSE 7 FL LIGHT FIXTURES AND OUTLETS ALONGWALLS EMT CONDUIT INSTALLED OUTDOOR
RSLV 09/18/2012 11/19/2012 11/27/2012
 
020 ( 4) SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL
BSMT SERVICE NEED NEW ADV BOARD DRAWINGS NOT A FINAL INSPECTION
RSLV 09/18/2012 11/19/2012 11/27/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order