| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
3 |
|
| E. Over 1200 AMPS |
1 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
67 |
|
| B. Over #2 to 1/0 |
1 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
10 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
67 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
5 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
2 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER FP AND FC - ALL |
RSLV |
05/04/2012 |
05/04/2012 |
06/19/2012 |
| |
| 002 |
(999) |
OTHER (A) SER.RM.FP - LINE AND LOAD ARE IN THE SAME ENCLOSURE WITH OTHERLOADS (695.3.A.1) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 003 |
(999) |
OTHER (B) SER. RM. FP - FP SER ENT IS IN THE SAME ENCLOSURE WITH OTHERLOADS (695.3.A.1) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 004 |
(999) |
OTHER (C) SERVICE SWITCH - GROUND RACEWAY IS NOT CONTINUOUS (250.64.E) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 005 |
(999) |
OTHER (D) SERVICE SUBFEEDERS NOT DERATED (TAB. 310.15.B.2.A) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 006 |
(999) |
OTHER (E) SERVICE ROOM - SERVCE ENTRANCE IS NOT 125% (695.6.C.(2) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 007 |
(999) |
OTHER (F) SERVICE ROOM - DISCONNECT IS NOT WITHIN 25FT OF TAP (240.21.B2(2) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 008 |
(999) |
OTHER (G) NEUTRAL BAR IS NOT BONDED AFTER SERVICE SWITCH (250.24(A)(5) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 009 |
(999) |
OTHER (H)GREENFIELD IS NOT GROUNDED (250.118(6) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 010 |
(999) |
OTHER (I)ENTIRE BUILDING - CONDUCTORS 4 AND LARGER NO BUSHING (300.4 F) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 011 |
(999) |
OTHER (J) NO ADVISORY BOARD APPROVAL (110.2.B AMENDMENT) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 012 |
(999) |
OTHER (K) ENTIRE BUILDING LIGHTS ARE NOT AFCI (210.12B) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 013 |
(999) |
OTHER (L) ENTIRE BUILDING - BALCONY OUTLETS ARE NOT ON GFCI (210.8) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 014 |
(999) |
OTHER (M) ENTIRE BUILDING - SMOKE DETECTORS ARE NOT AFCI (210.12B) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 015 |
(999) |
OTHER FP RM -FP WIRING IS NOT IN RIGID RACEWAY (695.6D) |
RSLV |
05/04/2012 |
06/19/2012 |
09/18/2012 |
| |
| 016 |
(105) |
TYPE EMT USED UNDERGROUND OR IN WET LOCATION THROUGHOUT FOR LIGHT OUTLET A/C UNIT |
RSLV |
06/19/2012 |
06/19/2012 |
09/18/2012 |
| |
| 017 |
(101) |
CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED NM CABLE USED FOR LIGHT OUTLET THROUGHOUT ROOF |
RSLV |
06/19/2012 |
06/19/2012 |
09/18/2012 |
| |
| 018 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT GROUND CONDUCTOR NOT TO LINE SIDE OF SERV SW |
RSLV |
09/18/2012 |
11/19/2012 |
11/27/2012 |
| |
| 019 |
(105) |
TYPE EMT USED UNDERGROUND OR IN WET LOCATION ROOF TERRACE OF PENT HOUSE 7 FL LIGHT FIXTURES AND OUTLETS ALONGWALLS EMT CONDUIT INSTALLED OUTDOOR |
RSLV |
09/18/2012 |
11/19/2012 |
11/27/2012 |
| |
| 020 |
( 4) |
SERVICE IN EXCESS OF 1000KVA HAS NOT BEEN SUBMITTED FOR APPROVAL BSMT SERVICE NEED NEW ADV BOARD DRAWINGS NOT A FINAL INSPECTION |
RSLV |
09/18/2012 |
11/19/2012 |
11/27/2012 |