BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B336418
Premises: 174 GARFIELD PLACE BROOKLYN BIN: 3020678     Block: 966   Lot: 25
   
Application Completed and Certified

Filed: 174 GARFIELD PL Census Tract:   1570 Health Area:  4500
ENTIRE BUILDING Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
Related Job Number:    320250429
DOB Cross Street(s):    6 AVENUE,    7 AVENUE
Status:   C - JOB IS SIGNED OFF 11/14/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/01/2011 6:08 PM
Application Entered:   03/01/2011 Job Start Date:   03/02/2011
Last Change:   11/14/2012 Job End Date:   03/01/2012
Appointment Status:   
Last Inspection By:   ROBINSON HEATH       On     11/08/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011392 Licensee Name: HOWARD M LEUNG
Firm: 003536 Firm Name: AERO ELECTRIC CORP
Firm Phone: 212-673-4383  Firm Address: 78 FORSYTH STREET, STE 1 NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $205.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANTHONY SAOUT
Owner Business Name: 174 GARFIELD PL. PROPERTY
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  1-100A SWITCH/PANEL COMBO
B. 101 Up to 200 AMPS  1  1-200A SWITCH
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  1-100A PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  1-200A PANEL
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS  20  20             
001  15  15             
002    15    15             
003    15    15             
Buildings Total 16  65  21  65                
Total Units : 169 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 3 - Removed Meters 3 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 03/01/2011 Notice: 1 - FIRST NOTICE 10/11/2012
Power Issued: 03/01/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B336418
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/01/2012 10/11/2012 DEX A E (60) (6) Y
INSPECTION COMMENTS: N
 
(2) 11/08/2012 11/14/2012 HRB C R E (70) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B336418
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO GROUND FOR (2) SERVICE ED TAPS
RSLV 10/01/2012 10/01/2012 11/08/2012
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROD RACEWAY NOT CONTINUOUS TO ROD
RSLV 10/01/2012 10/01/2012 11/08/2012
 
003 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
BASEMENT A/C UNIT NO DISCONNECT SWITCH
RSLV 10/01/2012 10/01/2012 11/08/2012
 
004 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
3RD FLOOR BEDROOM OUTLETS NOT AFCI PROTECTED
RSLV 10/01/2012 10/01/2012 11/08/2012
 
005 ( 17) DEFECTIVE SWITCHES ARE IN USE
4TH FLOOR BEDROOM AFCI BREAKER NOT TRIPPING
RSLV 10/01/2012 10/01/2012 11/08/2012
 
006 ( 18) DEFECTIVE RECEPTACLES ARE IN USE
ROOF DEFECTIVE GFCI OUTLET ON ROOF
RSLV 10/01/2012 10/01/2012 11/08/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order