BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B336095
Premises: 1715 KINGS HIGHWAY BROOKLYN BIN: 3182465     Block: 6780   Lot: 12
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 1632 E 18ST Census Tract:   5520 Health Area:  7320
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   T
BROOKLYN, NY 11229 Community Board:   315
DOB Cross Street(s):   AVENUE P,    KINGS HIGHWAY
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/18/2011 11:06 AM
Application Entered:   02/18/2011 Job Start Date:   02/18/2011
Last Change:   08/22/2025 Job End Date:   12/15/2011
Appointment Status:   
Last Inspection By:   PETER GREENE       On     08/15/2011      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011212 Licensee Name: PAUL LEFKOWITZ
Firm: 001756 Firm Name: BLZ ELECTRIC INC.
Firm Phone: 718-677-5900  Firm Address: 1243 EAST 15TH STREET BROOKLYN NY 11230 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
Total Fee:  $52.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: BRG 18 LLC
Authorized Representative:  R BAUER
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                     
Buildings Total                       
Total Units : 3 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 08/22/2011 Notice: 1 - FIRST NOTICE 08/22/2011
Power Issued: 08/22/2011 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B336095
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/15/2011 08/22/2011 PGR V E (55) (3) Y
INSPECTION COMMENTS: BOILER MOTOR 3 PHASE PLP IS 2 PHASE

OBJECTION FOR APPLICATION #: B336095
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
BSMT BOILER MOTOR IS 3 PHASE PLP IS SINGLE PHASE
OPEN 08/15/2011 08/15/2011
 
002 (243) CONDUCTORS OF THE SAME CIRCUIT NOT GROUPED
BSMT BOILER DISC/SW IS SINGLE PHASE MOTOR IS 3 PHASE
OPEN 08/15/2011 08/15/2011
 
003 ( 39) MOTOR NOT PROVIDED WITH PROPER RUNNING PROTECTION
BSMT 2 PHASE FROM PLP OTHER FROM TENANT METER
OPEN 08/15/2011 08/15/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.