BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B335468
Premises: 312 BEDFORD AVENUE BROOKLYN BIN: 3062940     Block: 2405   Lot: 23
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 312 BEDFORD AV Census Tract:   5510 Health Area:  0400
BASEMENT, 1-3 Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11211 Community Board:   301
DOB Cross Street(s):   SOUTH 1 STREET,    SOUTH 2 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/27/2011 1:18 PM
Application Entered:   01/27/2011 Job Start Date:   01/27/2011
Last Change:   08/22/2025 Job End Date:   01/27/2012
Appointment Status:   
Last Inspection By:   PETER GREENE       On     08/10/2011      
Field Disp:   V - OBJCTN ISSD: JOB INCOMPLT
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 011485 Licensee Name: BENJAMIN DREBIN
Firm: 002950 Firm Name: ACCURATE ELEC'L CORP.
Firm Phone: 718-606-9181  Firm Address: 11-07 43RD ROAD LONG ISLAND CITY NY 11101 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $321.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DAVID TABAK
Owner Business Name: 543 BEDFORD AVE INC
Authorized Representative:  DAVID TABAK
Relationship To Owner:   EC


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  5  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  2  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  3  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001      30    10  15         
002      30    10  15         
003      30    10  15         
Buildings Total   90    30  45              
Total Units : 174 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 1 #10-Wire 0
Existing Meters 5 + New Meters 5 - Removed Meters 5 = Total Meters 5

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 01/27/2011 Notice: 1 - FIRST NOTICE 08/15/2011
Power Issued: 01/27/2011 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B335468
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/10/2011 08/15/2011 PGR V E (60) (4) Y
INSPECTION COMMENTS: N/A TO APT 3 AND ROOF

OBJECTION FOR APPLICATION #: B335468
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BSMT 200 A SER/SW
OPEN 08/10/2011 08/10/2011
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GRN/FL 200A PANEL NEUTRAL BONDED
OPEN 08/10/2011 08/10/2011
 
003 ( 29) OUTLET BOXES ARE NOT COVERED
GRN/FL BOXES IN CEILING
OPEN 08/10/2011 08/10/2011
 
004 (101) CONDUCTORS AND/OR EQUIPMENT USED IS NOT APPROVED
APT 2 RELAY IN PANEL FOR A/C UNIT
OPEN 08/10/2011 08/10/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.