BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B335247
Premises: 1480 ATLANTIC AVENUE BROOKLYN BIN: 3397030     Block: 1203   Lot: 44
   
Application Completed and Certified

Filed: 1485 PACIFIC ST Census Tract:   3130 Health Area:  2900
1ST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11216 Community Board:   308
Special Place Name:   CROWN HEIGHTS CHARTER SCHOOL
Related Job Number:    310134468
DOB Cross Street(s):   BROOKLYN AVENUE,    KINGSTON AVENUE
Status:   C - JOB IS SIGNED OFF 05/12/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/20/2011 7:44 AM
Application Entered:   01/20/2011 Job Start Date:   01/20/2011
Last Change:   05/12/2011 Job End Date:   01/24/2011
Appointment Status:   
Last Inspection By:   SELF-CERTIFY       On     05/12/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 010807 Licensee Name: VINCENT DURYEE
Firm: 004095 Firm Name: HIG ELECTRIC ASSC NYC INC
Firm Phone: 718-204-0253  Firm Address: 8900 SUTPHIN BLVD SUITE LL 5 JAMAICA NY 11435 

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $40.00
Other Work:   REMOVAL OF VIOLATION
Violations To Be Removed That Were Issued To Or Filed By Another Licensed Firm:     B323848         
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:   No
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: RH ATLANTIC-PACIFIC LLC
Authorized Representative:  MICHAEL PARK
Relationship To Owner:   REP


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001                       
Buildings Total                       
Total Units : 3 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 04/06/2011
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  REMOVAL OF VIOLATIONS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B335247
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/08/2011 02/16/2011 NI1 A (55) (3) Y
INSPECTION COMMENTS: N
 
(2) 03/22/2011 04/06/2011 NI1 A R (150) (4) Y
INSPECTION COMMENTS: N
 
(3) 05/12/2011 05/12/2011 XXX C R (1) (0) Y
INSPECTION COMMENTS: SELF CERTIFICATION

OBJECTION FOR APPLICATION #: B335247
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
EMERGENCY FEEDERS ARE NOT 1 HOUR RATED (695.6.B.1)
RSLV 02/08/2011 02/08/2011 03/22/2011
 
002 (999) OTHER
EMERGENCY FEEDERS ARE NOT INDEPENDENT OF OTHERS (700.9.B)
RSLV 02/08/2011 02/08/2011 03/22/2011
 
003 (999) OTHER
CONTROL WIRING IS NOT 1 HOUR RATED (695.04.F)
RSLV 02/08/2011 02/08/2011 03/22/2011
 
004 (999) OTHER
EMERGENCY FEEDERS ARE NOT INDEPENDENT OF OTHER (700.9B)
RSLV 03/22/2011 03/22/2011 05/12/2011
 
005 (999) OTHER
FIRE PUMP GENERATOR FEEDER IS NOT ACCESSIBLE IN PULL BOXES (314.29)
RSLV 03/22/2011 03/22/2011 05/12/2011
 
006 (999) OTHER
EMERGENCY PULL BOXES, ENCLOSURE ARE NOT MARKED 700.0
RSLV 03/22/2011 03/22/2011 05/12/2011
 
007 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
BARRIERS IN EMERGENCY PULL BOXES
RSLV 03/22/2011 03/22/2011 05/12/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order