BIS Menu  |  Elevators  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B335110
Premises: 126 GREENPOINT AVENUE BROOKLYN BIN: 3064827     Block: 2563   Lot: 26
   
Application Completed and Certified

Filed: 126 GREENPOINT AV Census Tract:   5650 Health Area:  0100
2ND FLOOR & BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11222 Community Board:   301
DOB Cross Street(s):   FRANKLIN STREET,    MANHATTAN AVENUE
Status:   C - JOB IS SIGNED OFF 04/09/2014
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/13/2011 3:18 PM
Application Entered:   01/13/2011 Job Start Date:   01/13/2011
Last Change:   04/09/2014 Job End Date:   01/30/2012
Appointment Status:   
Last Inspection By:   BANYA, E       On     12/20/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011176 Licensee Name: JAMES J ZERVAS
Firm: 004379 Firm Name: D&D ELECTL CONST CO INC
Firm Phone: 212-524-9411  Firm Address: 18 WEST 27TH STREET, 12TH FLOOR NEW YORK NY 10001 

Historical Licensees and Firms:
License # Licensee Name Firm # Firm Name  
011176 ZERVAS, JAMES J 004077 D & D ELECTRIC CONTRG COR

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $366.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (1  Stores, 4 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FLORIN MEROVICHI
Owner Business Name: MEROVICHI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  400AMP
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  3 #6 THHN COPPER
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  4-500 KMCM COOPER
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  20 CIRCUIT 1-PHASE
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  12             
002  12             
002  12             
002  12             
Buildings Total 16  48  12  24  16                
Total Units : 116 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 4 + New Meters 4 - Removed Meters 1 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/13/2011 Notice: 1 - FIRST NOTICE 12/10/2013
Power Issued: 01/13/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B335110
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/03/2013 12/10/2013 EBA A E (60) (6) Y
INSPECTION COMMENTS: N
 
(2) 12/20/2013 12/23/2013 EBA C R E (60) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B335110
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
TROFT ON LINE SIDE OF S/S NOT BONDED. 250.58
RSLV 12/03/2013 12/03/2013 12/20/2013
 
002 (999) OTHER
COMMUNICATION BAR 250.54
RSLV 12/03/2013 12/03/2013 12/20/2013
 
003 (999) OTHER
AFCI NOT COMBINATION AFCI 210.12.B
RSLV 12/03/2013 12/03/2013 12/20/2013
 
004 (999) OTHER
A/C DISCONNECT IS NOT LOCKABLE AT COMPRESSOR 430.12
RSLV 12/03/2013 12/03/2013 12/20/2013
 
005 (999) OTHER
GFI NOT PROVIDED WITHIN 25 FT. A/C COMP 210.63
RSLV 12/03/2013 12/03/2013 12/20/2013
 
006 (999) OTHER
OUTLET NOT PROVIDED FOR PENINSULA 210.52.C.2
RSLV 12/03/2013 12/03/2013 12/20/2013