BIS Menu  |  Elevators  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B335048
Premises: 293 HOOPER STREET BROOKLYN BIN: 3063606     Block: 2463   Lot: 24
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 293 HOOPER ST Census Tract:   5270 Health Area:  0600
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11211 Community Board:   301
DOB Cross Street(s):   BROADWAY,    SOUTH 5 STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/12/2011 2:21 PM
Application Entered:   01/12/2011 Job Start Date:   01/13/2011
Last Change:   08/22/2025 Job End Date:   01/01/2012
Appointment Status:   
Last Inspection By:   JAMES CLANCY       On     05/16/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 009967 Licensee Name: SULPICE CHAMBLIN
Firm: 003265 Firm Name: PS&E ELECTRIC CONTRS INC
Firm Phone: 718-320-9400  Firm Address: 112-08 SPRINGFIELD BLVD QUEENS VILLAGE NY 11429 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
8 - BOILER/BURNER WIRING
9 - OTHER
T - TEMPORARY LIGHT & POWER
Total Fee:  $82.00
Other Work:   MOBILE BOILER
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:   B - BOILER CONTROLS J-51 CERTIFICATION
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ROBERT BAUER
Owner Business Name: 293-301 HOOPER STREET HOU
Authorized Representative:  ROBERT BAUER
Relationship To Owner:   AGENT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  1  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS               
Buildings Total                 
Total Units : 6 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 04/25/2011 Notice: 1 - FIRST NOTICE 05/22/2012
Power Issued: 04/25/2011 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B335048
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/21/2011 04/25/2011 FMO A E (15) (2) Y
INSPECTION COMMENTS: N
 
(2) 11/23/2011 11/28/2011 DEX N (20) (0) Y
INSPECTION COMMENTS: CONTRACTOR NO SHOW
 
(3) 05/16/2012 05/22/2012 JMZ A R (15) (2) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B335048
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
FEEDER TO PANEL NEUTRAL UNDERSIZE 250.66
RSLV 04/21/2011 04/21/2011 05/16/2012
 
002 ( 42) BUSHINGS ARE MISSING OR LOOSE
PLASTIC BUSHING MISSING IN PANEL 300.11 (A)
RSLV 04/21/2011 04/21/2011 05/16/2012
 
003 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
PANEL NEUTRAL FEED UNDERSIZED
OPEN 05/16/2012 05/16/2012
 
004 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
PANEL NEUTRALS ON GROUND BAR
OPEN 05/16/2012 05/16/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.