BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B333252
Premises: 325 A LEWIS AVENUE BROOKLYN BIN: 3045727     Block: 1655   Lot: 4
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 325A LEWIS AV Census Tract:   2950 Health Area:  3000
LEWIS AVE/3 FLOORS/8 ROOMS/1&2 Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11221 Community Board:   303
DOB Cross Street(s):   JEFFERSON AVENUE,    HANCOCK STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/05/2010 1:50 PM
Application Entered:   11/05/2010 Job Start Date:   11/10/2010
Last Change:   08/22/2025 Job End Date:   12/20/2010
Appointment Status:   
Last Inspection By:   JOHN, CHARLES       On     09/12/2012      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  

License #: 012171 Licensee Name: ROBERT JONES
Firm: 003882 Firm Name: F.I. ELECTRICAL CORP
Firm Phone: 718-986-8454  Firm Address: 34 MALCOLM X BLVD BROOKLYN NY 11221 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $40.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (1  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: VALERIE JONES
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 4 + New Meters 4 - Removed Meters 4 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 11/05/2010 Notice: 1 - FIRST NOTICE 09/17/2012
Power Issued: 11/05/2010 Response:  

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B333252
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/23/2012 08/27/2012 CJE N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 09/12/2012 09/17/2012 CJH A E (55) (5) Y
INSPECTION COMMENTS: CONTRACTOR SAID HE DID NOT RUN BRANCH FEEDERS CIRCUITS

OBJECTION FOR APPLICATION #: B333252
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (220) DOUBLE LUGGING IN SERVICE SWITCH
TWO CONDUCTOR UNDER ONE LUG BSMT PANEL 110.14A
OPEN 09/12/2012 09/12/2012
 
002 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NO PANEL DIRECTORY PROVIDED 408.4
OPEN 09/12/2012 09/12/2012
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
NO ELECTRICAL GROUND FOR SERVICE EQUIPTMENT 1,2
OPEN 09/12/2012 09/12/2012
 
004 ( 19) DEFECTIVE WIRING IS IN USE
APT #1 SWITCH NOT BOLTED TO ENCLOSURE 110.2A
OPEN 09/12/2012 09/12/2012
 
005 (999) OTHER
SPLICE BOXES FOR BRANCH FEEDER CIRCUITS 110
OPEN 09/12/2012 09/12/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.