BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B331595
Premises: 467 KEAP STREET BROOKLYN BIN: 3396771     Block: 2371   Lot: 42
   
Application Completed and Certified

Filed: 467 KEAP ST Census Tract:   5130 Health Area:  0700
ENTIRE Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11211 Community Board:   301
Related Job Number:    302372983
DOB Cross Street(s):   AINSLIE STREET,    UNION AVENUE
Status:   C - JOB IS SIGNED OFF 12/15/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/22/2010 8:47 PM
Application Entered:   09/22/2010 Job Start Date:   09/24/2010
Last Change:   12/15/2011 Job End Date:   09/24/2012
Appointment Status:   
Last Inspection By:   ISACC, N       On     11/23/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 009789 Licensee Name: LAWRENCE J NELSON
Firm: 001794 Firm Name: NELSON & TOM MAINT INC DB
Firm Phone: 212-233-0622  Firm Address: 29 EAST BROADWAY SUITE 201 NEW YORK NY 10002 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $1,553.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (2  Stores, 29 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: ANDY SIU
Owner Business Name: AINSLIE TOWER, LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  29  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  29  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    12    12             
BAS  COMM  10  20    10             
GND  COM  10  20    10             
LOB                   
SWL    24        24             
002  2A2B  13  42    14  13             
002  2C2D  11  40    13  11             
003  3A3B  13  42    14  13             
003  3C3D  11  40    13  11             
004  4A4B  13  42    14  13             
004  4C4D  11  40    13  11             
005  5A5B  13  42    14  13             
005  5C5D  11  40    13  11             
006  6A6B  13  42    14  13             
006  6C6D  11  40    13  11             
007  7A7B  13  42    14  13             
007  7C7D  11  40    13  11             
008  8A8B  13  42    14  13             
008  8C  23               
009  9B  23               
PEN    11  35    13  11             
ROF          29  58         
Buildings Total 251  663    237  236     58           
Total Units : 1445 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 10/24/2011
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING ONLY - SERVICE WORK FILED UNDER ANOTHER APPLICATION

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B331595
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/18/2011 10/24/2011 DEX V (50) (2) Y
INSPECTION COMMENTS: N
 
(2) 11/23/2011 12/08/2011 NI1 C R (90) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B331595
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 53) GFCI HAS NOT BEEN PROVIDED
THROUGHOUT - ALL OUTLETS NEXT TO SINKS THROUGHOUT BUILDING OUTLETSNOT GFI PROTECTED
RSLV 10/18/2011 10/18/2011 11/23/2011
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
THROUGHOUT - ALL OUTLETS THROUGHOUT BUILDING NOT GROUNDED PROPERLY
RSLV 10/18/2011 10/18/2011 11/23/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.