BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B331116
Premises: 325 3 STREET BROOKLYN BIN: 3020915     Block: 974   Lot: 61
   
Application Completed and Certified

Filed: 325 3 ST Census Tract:   1350 Health Area:  4200
2B 2C 1C 1A Admin Area:   B - BROOKLYN Inspection Area:   D
BROOKLYN, NY 11215 Community Board:   306
DOB Cross Street(s):    4 AVENUE,    5 AVENUE
Status:   C - JOB IS SIGNED OFF 11/08/2010
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   09/22/2010 Job Start Date:   09/22/2010
Last Change:   11/08/2010 Job End Date:   09/20/2011
Appointment Status:   
Last Inspection By:   ISACC, N       On     10/28/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010730 Licensee Name: ALBERT MARGOLIN
Firm: 003031 Firm Name: GSA ELECTRIC CORP.
Firm Phone: 718-922-3300  Firm Address: 9302 DITMAS AVENUE BROOKLYN NY 11236 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
012290 MARGOLIN, GREGG 003031 GSA ELECTRIC CORP. RESPONSIBLE REP

Work Started or Filed by Others: YES
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $280.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FELIX ORBE
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  4  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  4  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
002  2B                 
Buildings Total                   
Total Units : 4 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/08/2010 Notice: 1 - FIRST NOTICE 10/01/2010
Power Issued: 11/08/2010 Response: F - FILED TO REMOVE OBJECTION 09/22/2010

Follow-Up: X - FILED APPL,NOW CLOSED 09/22/2010
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B331116
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/31/2010 09/09/2010 PGR W (5) (8)
INSPECTION COMMENTS: N
 
(2) 09/30/2010 10/01/2010 NI1 A Y (65) (0) Y
INSPECTION COMMENTS: APARTMENT 1A OK
 
(3) 10/28/2010 11/08/2010 NI1 C R E (35) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B331116
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
FOR LIGHT SWITCH OUTLET PANEL TO APT 2B 2C 1C 1A FEEDER TO ALL APTIN THE BUILDING
RSLV 08/31/2010 08/31/2010 09/30/2010
 
002 ( 34) KNOCKOUTS ARE NOT CLOSED IN PANEL BOX
APT 2B
RSLV 08/31/2010 08/31/2010 09/30/2010
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
APT 2B
RSLV 08/31/2010 08/31/2010 09/30/2010
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
LIGHT UNDER KITCHEN CABINET 2B
RSLV 08/31/2010 08/31/2010 09/30/2010
 
005 (999) OTHER
KITCHEN OUTLET WITH LIGHT 210.52 2B
RSLV 08/31/2010 08/31/2010 09/30/2010
 
006 (999) OTHER
KITCHEN TWO CIRCUIT NOT PROVIDED ON COUNTER TOP 210.52 2B
RSLV 08/31/2010 09/30/2010 10/28/2010
 
007 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
BEDROOM 2B
RSLV 08/31/2010 09/30/2010 10/28/2010
 
008 (999) OTHER
OUTLET GFCI THROUGHOUT 250.146 2B
RSLV 08/31/2010 09/30/2010 10/28/2010