BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B330604
Premises: 239 EAST 51 STREET BROOKLYN BIN: 3100879     Block: 4638   Lot: 40
   
Application Completed and Certified

Filed: 239 E 51ST ST Census Tract:   8680 Health Area:  5510
BSMT,1ST,2ND,3RD FLS Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11203 Community Board:   317
Special Place Name:   BROOKLYN
DOB Cross Street(s):   CLARKSON AVENUE,    LENOX ROAD
Status:   C - JOB IS SIGNED OFF 06/28/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  08/25/2010 2:29 PM
Application Entered:   08/25/2010 Job Start Date:   08/26/2010
Last Change:   06/28/2012 Job End Date:   10/31/2010
Appointment Status:   
Last Inspection By:   PETER GREENE       On     06/21/2012      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010809 Licensee Name: JOHN L RICKFORD
Firm: 002075 Firm Name: R.J.ELECTRICAL CONTRACTOR
Firm Phone: 718-949-5466  Firm Address: 201-11 LINDEN BLVD ST. ALBANS NY 11412 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $220.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SHIRLEY TUITT
Owner Business Name: NONE
Authorized Representative:  RICKFORD JOHN
Relationship To Owner:   ELECTRICAL CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  1  1-200 AMP MAIN
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  1-SET OF 3 #3/0 AWG
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  7  7-10/20 PANELS
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 7 #4-Wire 0 #10-Wire 0
Existing Meters 7 + New Meters 7 - Removed Meters 7 = Total Meters 7

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 08/25/2010 Notice: 1 - FIRST NOTICE 10/05/2011
Power Issued: 08/25/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  UPGRADE ELECTRICAL SERVICE TO 200 AMPS 3-WIRE 110/208 VOLTSFOR SIX (6) APARTMENTS AND ONE (1) PLP. NO OTHER WORK DONE

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B330604
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/27/2011 10/05/2011 JMZ A E (60) (2) Y
INSPECTION COMMENTS: N
 
(2) 05/08/2012 05/10/2012 PGR J Y E (40) (0) Y
INSPECTION COMMENTS: N
 
(3) 06/21/2012 06/26/2012 PGR C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B330604
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
SIX FAMILY BUILDING SERVICE SWITCH OUTSIDE
RSLV 09/27/2011 09/27/2011 05/08/2012
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUND OUTSIDE FLEX FEEDER
RSLV 09/27/2011 05/08/2012 06/21/2012



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.