Electrical Application Details for App #: B326648
Premises: 285 LIVINGSTON STREET BROOKLYN BIN: 3000482     Block: 161   Lot: 64
   

Filed: 285 LIVINGSTON ST Census Tract:   37 Health Area:  2400
GROUND Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11217 Community Board:   302
DOB Cross Street(s):   HANOVER PLACE,    NEVINS STREET
Status:   K - CLOSED/CANCELLED 07/10/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/28/2010 9:02 AM
Application Entered:   04/28/2010 Job Start Date:   04/28/2010
Last Change:   07/10/2012 Job End Date:   04/01/2011
Appointment Status:   
Last Inspection By:   MOSES, FITZROY       On     07/03/2012      
Field Disp:   K - OK TO CANCEL
Energize Recommendation:  
Objection Disposition:  

License #: 012001 Licensee Name: PATRICK M WOODWORTH
Firm: 004037 Firm Name: JYC ELECTRIC CONTRG INC
Firm Phone: 212-941-8888  Firm Address: 401 BROADWAY SUITE 2308 NEW YORK NY 10013 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $68.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   RESALE- PC
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: PAT FIERO
Owner Business Name: 285 LIVINGSTON ST
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND        80  32         
Buildings Total     80  32              
Total Units : 125 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: R - OBJECTION(S) RESOL
Power Requested: Notice: 1 - FIRST NOTICE 05/22/2012
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B326648
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/06/2011 06/10/2011 DEX N (45) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 09/22/2011 09/23/2011 PGR P (50) (0) Y
INSPECTION COMMENTS: CONT NO SHOW
 
(3) 05/14/2012 05/22/2012 JMZ A (45) (7) Y
INSPECTION COMMENTS: PICK UP PANEL APPLICATION FEED WH CONDUCTOR INSIDE AIR HANDLER NOT ACCESSIBLE
 
(4) 07/03/2012 07/10/2012 FMO K (5) (0) Y
INSPECTION COMMENTS: CONTRACTOR CANCELLED

OBJECTION FOR APPLICATION #: B326648
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUND RECEPTACLES TO BOX
RSLV 05/14/2012 05/14/2012 07/03/2012
 
002 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
SUPPORT FIXTURES DROP CEILING
RSLV 05/14/2012 05/14/2012 07/03/2012
 
003 ( 13) THE CONDUCTORS FEEDING THE MOTORS ARE NOT OF PROPER SIZE
ROOF A/C FEED NOT SUFFICIENT
RSLV 05/14/2012 05/14/2012 07/03/2012
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF A/C GROUND NOT SUFFICIENT
RSLV 05/14/2012 05/14/2012 07/03/2012
 
005 ( 53) GFCI HAS NOT BEEN PROVIDED
ROOF A/C NO GFCI
RSLV 05/14/2012 05/14/2012 07/03/2012
 
006 ( 41) LOCKNUTS ARE NOT MADE UP TIGHT
ROOF A/C LOCK NUTS LOOSE
RSLV 05/14/2012 05/14/2012 07/03/2012
 
007 ( 8) CONDUIT IS NOT PROPERLY SUPPORTED (TYPE:IMC)
ROOF A/C SUPPPORT CONDUITS
RSLV 05/14/2012 05/14/2012 07/03/2012