BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B326102
Premises: 37 HICKS STREET BROOKLYN BIN: 3001540     Block: 211   Lot: 1
   

DOB NOW: Inspections

Application Completed and Certified

Filed: 37 HICKS ST Census Tract:   1 Health Area:  2300
POPLAR ST. Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
Special Place Name:   P.S. 8
DOB Cross Street(s):   POPLAR STREET,    MIDDAGH STREET
Status:   C - JOB IS SIGNED OFF 03/23/2018
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  04/12/2010 12:11 PM
Application Entered:   04/12/2010 Job Start Date:   06/15/2010
Last Change:   03/23/2018 Job End Date:   12/07/2010
Appointment Status:   
Last Inspection By:   JOHN HUGHES       On     03/22/2018      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  
Objection Disposition:  R - REMOVED

License #: 011684 Licensee Name: MIKHAIL BEKKERMAN
Firm: 003267 Firm Name: STAR ELEC'L CONTRACTORS C
Firm Phone: 718-208-8231  Firm Address: 110 SHORE BLVD SUITE 5J BROOKLYN NY 11235 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
3 - ELEVATOR/ESCALATOR/MATERIAL LIFT
Total Fee:  $290.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   W - School
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: BRUCE BARRETT
Owner Business Name: NYC SCHOOL CONSTRUCTION A
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  2  250.00
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag:
Power Requested: Notice: 1 - FIRST NOTICE 08/28/2013
Power Issued: Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B326102
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/19/2013 08/28/2013 CJH A (35) (4) Y
INSPECTION COMMENTS: -
 
(2) 02/22/2018 02/22/2018 OSZ J Y (20) (0)
INSPECTION COMMENTS: OBJECTION HAS NOT BEEN RESOLVED.
 
(3) 03/22/2018 03/23/2018 JGX C R (13) (0)
INSPECTION COMMENTS: OUTSTANDING OBJECTION RESOLVED.

OBJECTION FOR APPLICATION #: B326102
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
(ALL FLOORS)BASE: CAB LIGHTS DIS-SWITCHES TWO CONDUCTOR ONE LUG 110.14
RSLV 08/19/2013 08/19/2013 02/22/2018
 
002 (999) OTHER
(ALL FLOORS)BASE: ZIP SCREW USED TO TERMINATE GRN LUGS IN CAR LIGHTS 250.8
RSLV 08/19/2013 08/19/2013 02/22/2018
 
003 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
(ALL FLOORS)BASE: CAB LIGHTS DIS-CONNECT #12 CONDUCTOR ON 30A BRAKES 240.3
RSLV 08/19/2013 08/19/2013 03/22/2018
 
004 (129) SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE
(ALL FLOORS) BASE: ELEVATORS DIS.CONNECT SWITCHES 250.24(A5)
RSLV 08/19/2013 08/19/2013 02/22/2018



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.