BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B325150
Premises: 121 WATER STREET BROOKLYN BIN: 3388012     Block: 28   Lot: 7501
   
Application Completed and Certified

Filed: 31 WASHINGTON ST Census Tract:   21 Health Area:  1000
1`ST FL APT Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   302
DOB Cross Street(s):   PLYMOUTH STREET,    WATER STREET
Status:   C - JOB IS SIGNED OFF 11/02/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  03/11/2010 9:07 PM
Application Entered:   03/11/2010 Job Start Date:   05/30/2010
Last Change:   11/02/2011 Job End Date:   05/15/2011
Appointment Status:   
Last Inspection By:   MOSES, FITZROY       On     09/14/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012097 Licensee Name: BORIS NASIMOV
Firm: 003794 Firm Name: NAS ELECTRIC CORP
Firm Phone: 718-837-0737  Firm Address: 65-35 AUSTIN STREET REGO PARK NY 11374 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
Total Fee:  $132.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   A - One Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MICHAL WEGLESKI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    20  30    10  20             
Buildings Total 20  30    10  20                
Total Units : 80 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 01/28/2011 Notice: 1 - FIRST NOTICE 04/25/2011
Power Issued: 01/28/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  GENERAL WIRING

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B325150
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/12/2010 11/16/2010 PAT N (20) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(2) 01/25/2011 01/28/2011 FMO A E (40) (5) Y
INSPECTION COMMENTS: 6TH FLOOR APT FEEDERS TO PANELS EXISTING
 
(3) 04/21/2011 04/25/2011 DEX A Y (50) (0) Y
INSPECTION COMMENTS: STUDIO APARTMENT
 
(4) 09/14/2011 09/16/2011 FMO C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B325150
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
OUTLETS THROUGHOUT APT NOT GROUNDED 250.122
RSLV 01/25/2011 01/25/2011 04/21/2011
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
FIXTURES HANGING NOT PROPERLY GROUNDED 250.122
RSLV 01/25/2011 01/25/2011 04/21/2011
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
PANEL GROUND WIRE NOT PROPERLY TERMINATED 250.122
RSLV 01/25/2011 01/25/2011 04/21/2011
 
004 (999) OTHER
OUTLET ON ISLAND MORE THAN 12 INCHES OVER HANG 210.52 (C1)
RSLV 01/25/2011 01/25/2011 04/21/2011
 
005 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
NO AFCI PROVIDED IN SLEEPING AREA 210.12B
RSLV 01/25/2011 04/21/2011 09/14/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.