Electrical Application Details for App #: B324277
Premises: 443 WINTHROP STREET BROOKLYN BIN: 3404051     Block: 4820   Lot: 42
   
Application Completed and Certified

Filed: 443 WINTHROP ST Census Tract:   810 Health Area:  4800
BASEMENT,1,2,3,4,5,6,7,ROOF FL Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11203 Community Board:   309
Related Job Number:    310248817
DOB Cross Street(s):   NEW YORK AVENUE,    BROOKLYN AVENUE
Status:   C - JOB IS SIGNED OFF 06/21/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/05/2010 1:29 PM
Application Entered:   02/05/2010 Job Start Date:   02/10/2010
Last Change:   06/21/2011 Job End Date:   02/10/2010
Appointment Status:   
Last Inspection By:   PETER GREENE       On     06/08/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010895 Licensee Name: IRVING PURCELL
Firm: 002178 Firm Name: PURCELL ELEC'L CONTRS LTD
Firm Phone: 718-341-4779  Firm Address: 10701 GUY R BREWER BLVD JAMAICA NY 11433 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $1,987.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MOSHE ZLICHA
Authorized Representative:  MOSHE ZLICHA
Relationship To Owner:   SELF


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  1-400AMP
D. 601 Up to 1200 AMPS  1  1-1000AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  21  21SETS#2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  2SETS #3/0
D. Over 250 MCM  5  2 SET 350MCM,3 SET 500MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  18  18-1PH 20 CB
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  4  4 - 3PH 200AMP
D. 3 Phase Over 225 AMPS  1  1-3PH 400AMP
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS    40  40    22  40  50         
001    28    28             
002    30  24    16  30         
003    28  74  25  28             
004    28  74  25  28             
005    28  74  25  28             
006    28  74  25  28             
007    25  60  20  25             
ROF    14    14  10         
Buildings Total 249  428  37  164  249     52           
Total Units : 1179 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 18 #4-Wire 2 #10-Wire 1
Existing Meters 0 + New Meters 21 - Removed Meters 0 = Total Meters 21

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/05/2010 Notice: 1 - FIRST NOTICE 05/23/2011
Power Issued: 02/05/2010 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  18 FAMILY MULTI USE DWELLING.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B324277
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 05/18/2011 05/23/2011 JMZ A E (75) (3) Y
INSPECTION COMMENTS: INSPECTION COMPLETED
 
(2) 06/08/2011 06/10/2011 PGR C R E (5) (0) Y
INSPECTION COMMENTS: SEE ATT LETTER

OBJECTION FOR APPLICATION #: B324277
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 12) SERVICE CONDUCTORS ARE NOT OF THE PROPER SIZE
1200 AMP SERVICE SWITCH (3) 500 MCM
RSLV 05/18/2011 05/18/2011 06/08/2011
 
002 ( 28) ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED
FIRE PUMP FEEDER CONCRETE NOT 2 INCHES IN GAS ROOM
RSLV 05/18/2011 05/18/2011 06/08/2011
 
003 ( 11) FEEDER CONDUCTORS ARE NOT OF PROPER SIZE
1200 AMP FEEDER (3) 500 MCM
RSLV 05/18/2011 05/18/2011 06/08/2011