Electrical Application Details for App #: B323937
Premises: 126 GREENPOINT AVENUE BROOKLYN BIN: 3064827     Block: 2563   Lot: 26
   
Application Completed and Certified

Filed: 126 GREENPOINT AV Census Tract:   565 Health Area:  0100
ROOF/ BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   A
BROOKLYN, NY 11222 Community Board:   301
DOB Cross Street(s):   FRANKLIN STREET,    MANHATTAN AVENUE
Status:   C - JOB IS SIGNED OFF 11/03/2011
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  01/26/2010 9:39 AM
Application Entered:   01/26/2010 Job Start Date:   05/01/2010
Last Change:   11/03/2011 Job End Date:   10/30/2010
Appointment Status:   
Last Inspection By:   HUGH MCKESSEY       On     11/02/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011497 Licensee Name: ARIE BAR
Firm: 002968 Firm Name: AARCO ELECTRIC, INC
Firm Phone: 718-531-1114  Firm Address: 5902 AVENUE N BROOKLYN NY 11234 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
9 - OTHER
S - SUSTAINABLE ENERGY - GENERAL
Total Fee:  $100.50
Other Work:   SOLAR SYSTEM
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   I - Hospital Or Health Facility
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: GREENPOINT AVE EQUITIES L
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  3 PHASE 100AMPS
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  3 PHASE 100 AMPS
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
ROF              20  20         
Buildings Total              20           
Total Units : 20 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/03/2011 Notice: 1 - FIRST NOTICE 10/11/2011
Power Issued: 11/03/2011 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW 20KW SOLAR SYSTEM

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B323937
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 02/09/2010 02/12/2010 MC2 N (15) (0)
INSPECTION COMMENTS: NO SHOW
 
(2) 10/05/2011 10/11/2011 PAT V (45) (3) Y
INSPECTION COMMENTS: NOT A FINAL INSPECTION
 
(3) 11/02/2011 11/03/2011 HMC C R E (20) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B323937
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
ROOF - WARNING LABEL IS NOT PROVIDED AT INVERTER OR AT A VISIBLELOCATION 690.5K
RSLV 10/05/2011 10/05/2011 11/02/2011
 
002 (999) OTHER
ROOF - NO MORE THAN SIDE DISCONNECT OR CIRCUIT BREAKERS MOUNTED IN ASINGLE ENCLOSURE 690.14CK
RSLV 10/05/2011 10/05/2011 11/02/2011
 
003 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
BASEMENT - SOLAR SYSTEM GROUND NOT COMING FROM THE WATER MAIN
RSLV 10/05/2011 10/05/2011 11/02/2011