| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
1 @30 |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
4 |
2@4K,1@2K,1@1600 |
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
12 |
(7)#8, (2) #6, (3) #4 |
| B. Over #2 to 1/0 |
11 |
(6)1/0,(5) #1 |
| C. Over 1/0 to 250 MCM |
28 |
(5)@250,(4)@500,(11)@350 |
| D. Over 250 MCM |
32 |
(17)@600,(4)@500,(11)350 |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
24 |
16 @225, 8 @ 100 |
| D. 3 Phase Over 225 AMPS |
9 |
1 @800, 3 @600, 5 @400 |
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER SERVICE ENTRANCE BONDING IS NOT 12 1/0 OF TOTAL MCM 250.24.B.1SERRVICE ENT BONDING IS LOOPED) |
RSLV |
08/19/2010 |
08/19/2010 |
09/17/2010 |
| |
| 002 |
(999) |
OTHER WIRING FROM EMERGENCY SOURCE SHALL BE KEPT AND RELY INDEPENDENT OFALL OTHER WIRING 700.9B ( IN SAME SPLICE BOX WITH BARRIER) |
RSLV |
08/19/2010 |
08/19/2010 |
09/17/2010 |
| |
| 003 |
(999) |
OTHER EMERGENCY FEEDERS AND BRANCH CIRCUIT IS NOT 1 HOUR FIRE RATED700.9.0.1 |
RSLV |
08/19/2010 |
08/19/2010 |
09/17/2010 |
| |
| 004 |
(999) |
OTHER EMERGENCY SOURCE IS NOT INDEPENDENT OF OTHER WIRING |
RSLV |
09/17/2010 |
09/17/2010 |
02/08/2011 |
| |
| 005 |
(999) |
OTHER FENCE IS NOT PROVIDED REAR FOR FRONT ACCESS SERVICE SWITCH 230.6.B.4 |
RSLV |
09/17/2010 |
09/17/2010 |
02/08/2011 |
| |
| 006 |
(999) |
OTHER EMERGENCY FEEDERS ARE NOT 1 HOUR RATED 695.6.B.1.C |
RSLV |
02/08/2011 |
02/08/2011 |
03/22/2011 |
| |
| 007 |
(999) |
OTHER EMERGENCY FEEDERS ARE NOT INDEPENDENT OF OTHERS (700.9.B) |
RSLV |
02/08/2011 |
02/08/2011 |
03/22/2011 |
| |
| 008 |
(999) |
OTHER CONTROL WIRING IS NOT 1 HOUR RATED 695.14.F |
RSLV |
02/08/2011 |
02/08/2011 |
03/22/2011 |
| |
| 009 |
(999) |
OTHER EMERGENCY FEEDERS ARE NOT INDEPENDENT AT OTHER (700.9.B) |
RSLV |
03/22/2011 |
03/22/2011 |
05/12/2011 |
| |
| 010 |
(999) |
OTHER FIRE PUMP GENERATOR FEEDER ARE NOT ACCESSIBLE IN PULL BOXES (314.29) |
RSLV |
03/22/2011 |
03/22/2011 |
05/12/2011 |
| |
| 011 |
(999) |
OTHER EMERGENCY PULL BOXES, PANEL, RACEWAY ARE NOT MARKED 700.9 |
RSLV |
03/22/2011 |
03/22/2011 |
05/12/2011 |
| |
| 012 |
( 28) |
ELECTRICAL MATERIAL USED FOR LUMINAIRES HAS NOT BEEN APPROVED BARRIERS IN EMERGENCY PULL BOXES |
RSLV |
03/22/2011 |
03/22/2011 |
05/12/2011 |