BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B323516
Premises: 6 SHORE BOULEVARD BROOKLYN BIN: 3245439     Block: 8710   Lot: 35
   

DOB NOW: Inspections


Filed: 2 NEPTUNE AV Census Tract:   610.01 Health Area:  9120
BSMT Admin Area:   B - BROOKLYN Inspection Area:   R
BROOKLYN, NY 11235 Community Board:   315
DOB Cross Street(s):   EAST 14 STREET,    CASS PLACE
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   01/08/2010 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   COHN, MARTIN       On     01/05/2010      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   BAGEL STORE
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup: DELMAN LLC
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 01/08/2010
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 01/08/2010
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B323516
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/05/2010 01/08/2010 MC2 W (90) (8)
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B323516
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
NO APP ON FILE ELECTRICAL WIRING OF DIS SW TO STORE #1TAP FEEDING SW RISERS TO STORE PANEL 27.3017A
OPEN 01/05/2010 01/05/2010
 
002 (999) OTHER
CONNECTION IN FUSE CABINET LOCATED IN BSMT DOUBLE LUGGED 110.14A
OPEN 01/05/2010 01/05/2010
 
003 (999) OTHER
DIS SWITCH NOT SECURED TO WALL 110.2
OPEN 01/05/2010 01/05/2010
 
004 ( 19) DEFECTIVE WIRING IS IN USE
DEFECTIVE WIRING TAP TO PANEL IN STORE BSMT DAMAGED TO BE REPLACED110.2
OPEN 01/05/2010 01/05/2010
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
DETERIATED SERVICE GROUND AT WATER MAIN 250.112
OPEN 01/05/2010 01/05/2010
 
006 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
DRIVEN GROUND NOT PROVIDED 250.92CA
OPEN 01/05/2010 01/05/2010
 
007 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
GROUNDING JUMPER WATER MAIN AND WATER METER NOT PROVIDED
OPEN 01/05/2010 01/05/2010
 
008 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
600A SERVICE SWITCH NEUTRAL NOT BONDED TO ENCLOSURE 250.112
OPEN 01/05/2010 01/05/2010