| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
1 |
SET OF # 2'S |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
1 |
40 CIRCUIT PANEL |
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER A/C COMPRESSOR DIS SWITCH MIN 3FT SPACE NOT PROVIDED 110.26 |
OPEN |
03/31/2010 |
03/31/2010 |
|
| |
| 002 |
(999) |
OTHER A/C DIS SW GROUNDING CONDUCTORS STRANDED NOT TERMINATED IN LUG |
OPEN |
03/31/2010 |
03/31/2010 |
|
| |
| 003 |
( 15) |
FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD A/C BLOWER FLEXIBLE AS PERMANENT WIRING METHOD 408.8 |
OPEN |
03/31/2010 |
03/31/2010 |
|
| |
| 004 |
( 36) |
CONDUCTORS ARE NOT PROPERLY COLOR CODED WIRES RUN IN EMT TO 42 CKT PANEL BLUE CONDUCTOR REIDENTIFIED WITHTYPE NOT #4 LARGER NOT PROVIDED 210.43 210.J |
OPEN |
03/31/2010 |
03/31/2010 |
|
| |
| 005 |
( 19) |
DEFECTIVE WIRING IS IN USE F.A GND DOUBLE LUGED AT WATER MAIN 110.14A |
OPEN |
03/31/2010 |
03/31/2010 |
|
| |
| 006 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY GND CONDUCTORS NOT PROPERLY TERMINATED 250.24 |
OPEN |
03/31/2010 |
03/31/2010 |
|
| |
| 007 |
(999) |
OTHER F.A CUT OUT WIRES TERMINATION USE DOUBLE LUGED 110.14PANEL RISERS IN BSMT ARMORED CABLES NOT SUPPORTED 320.3A |
OPEN |
03/31/2010 |
03/31/2010 |
|
| |
| 008 |
(999) |
OTHER RISE DIS PANEL F.A TAPS DOUBLE LUGGED 110.14A |
OPEN |
03/31/2010 |
03/31/2010 |
|
| |
| 009 |
( 34) |
KNOCKOUTS ARE NOT CLOSED IN PANEL BOX RISE DIS PANEL KO SEALS NOT PROVIDED 110.12A |
OPEN |
03/31/2010 |
03/31/2010 |
|