BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B322716
Premises: 2969 OCEAN AVENUE BROOKLYN BIN: 3204409     Block: 7441   Lot: 242
   
Application Completed and Certified

Filed: 2969 OCEAN AV Census Tract:   594.01 Health Area:  8722
3RD FLOOR Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11235 Community Board:   315
DOB Cross Street(s):   AVENUE Y,    AVENUE Z
Status:   C - JOB IS SIGNED OFF 04/29/2013
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/05/2009 11:13 AM
Application Entered:   12/05/2009 Job Start Date:   12/07/2009
Last Change:   04/29/2013 Job End Date:   12/30/2009
Appointment Status:   
Last Inspection By:   CHARLES COURTNEY       On     03/13/2013      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011196 Licensee Name: PRAMANAND RAMBHAROSE
Firm: 002163 Firm Name: WINDSOR ELEC CONT'G INC.
Firm Phone: 718-850-6523  Firm Address: 95-01 BRISBIN STREET JAMAICA NY 11435 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $84.75
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JHONNY MUSEAFOSKI
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  3-NO. 2
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  12 POLES
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
003    15  25  10  15             
Buildings Total 15  25  10  15                
Total Units : 69 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 1 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/05/2009 Notice: 1 - FIRST NOTICE 02/23/2013
Power Issued: 12/05/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  3RD FLOOR APARTMENT

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B322716
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 06/27/2012 07/03/2012 JMZ A E (60) (6) Y
INSPECTION COMMENTS: N
 
(2) 07/30/2012 08/06/2012 HRB J Y E (35) (0) Y
INSPECTION COMMENTS: N
 
(3) 09/12/2012 09/15/2012 RHO N (15) (0) Y
INSPECTION COMMENTS: N
 
(4) 10/17/2012 10/22/2012 PAT N (30) (0) Y
INSPECTION COMMENTS: NO SHOW
 
(5) 12/12/2012 12/17/2012 CJE N (35) (0) Y
INSPECTION COMMENTS: N
 
(6) 02/19/2013 02/23/2013 CJH A R E (5) (1) Y
INSPECTION COMMENTS: N
 
(7) 03/13/2013 03/19/2013 CCH C R E (80) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B322716
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
BOND 3RD FLOOR SERVICE SWITCH RACEWAY
RSLV 06/27/2012 06/27/2012 07/30/2012
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
2 TAPS END BOX NEED ADDITIONAL WATER GROUND
RSLV 06/27/2012 07/30/2012 02/19/2013
 
003 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
MARK 3RD FLOOR SERVICE SWITCH
RSLV 06/27/2012 07/30/2012 02/19/2013
 
004 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
3RD FLOOR FRONT BEDROOM NO A/C RECEPTICAL
RSLV 06/27/2012 07/30/2012 02/19/2013
 
005 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
3RD FLOOR PHASE PANEL (3) WIRE CONDUCTORS
RSLV 06/27/2012 07/30/2012 02/19/2013
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
3RD FLOOR (3) WIRE CONDUCTORS ON SINGLE POLE AFCI
RSLV 06/27/2012 07/30/2012 02/19/2013
 
007 (128) NEUTRAL IS GROUNDED BEYOND LOAD SIDE OF SERVICE SWITCH
3RD FLOOR PANEL 250.24 (A5)
RSLV 02/19/2013 02/19/2013 03/13/2013



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.