BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B321800
Premises: 1901 EMMONS AVENUE BROOKLYN BIN: 3326914     Block: 8775   Lot: 41
   

DOB NOW: Inspections


Filed: 1901 EMMONS AV Census Tract:   608 Health Area:  8721
BASEMENT TO FIRST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11235 Community Board:   315
DOB Cross Street(s):   EAST 19 STREET,    OCEAN AVENUE
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   NO
Application Entered:   11/04/2009 Job Start Date:  
Last Change:   08/22/2025 Job End Date:  
Appointment Status:   
Last Inspection By:   JAMES CLANCY       On     10/28/2009      
Field Disp:   W - ISSUE OBJECTION TO OWNER
Energize Recommendation:  
Objection Disposition:  

License #: Licensee Name: UNKNOWN
Firm: Firm Name: UNKNOWN
Firm Phone:   Firm Address:  

Work Started or Filed by Others: NO
Work Category:    Work To Be Done:   Total Fee:  $0.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   K - Store
Store / Other:   FOOD
Special Cert Approval:  
Advisory Board Approval:  
Owner / Occup:
Owner Business Name: CHERRY HILL
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: Objection Flag: V - OBJECTION(S) EXIST
Power Requested: Notice: 1 - FIRST NOTICE 11/04/2009
Power Issued: Response:  

Follow-Up: V - OWNER OBJECTION 11/04/2009
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B321800
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/28/2009 11/04/2009 JMZ W (15) (7)
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B321800
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
KITCHEN EXISTING PANEL TRIM MISSING
OPEN 10/28/2009 10/28/2009
 
002 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
KITCHEN FLRX CORDS
OPEN 10/28/2009 10/28/2009
 
003 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
BASEMENT DEFECTIVE LIGHTING
OPEN 10/28/2009 10/28/2009
 
004 ( 19) DEFECTIVE WIRING IS IN USE
BASEMENT DEFECTIVE WIRING AND RECEPTACLE
OPEN 10/28/2009 10/28/2009
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT SUMP PUMP MISSING GROUND
OPEN 10/28/2009 10/28/2009
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BASEMENT GELATO CASE TRANSFORMER GROUNDED TO WATER
OPEN 10/28/2009 10/28/2009
 
007 ( 29) OUTLET BOXES ARE NOT COVERED
BASEMENT PANEL COVER MISSING
OPEN 10/28/2009 10/28/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order