BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B321735
Premises: 164 PACIFIC STREET BROOKLYN BIN: 3003062     Block: 292   Lot: 11
  Printable (PDF) version of this Permit  

DOB NOW: Inspections


Filed: 164 PACIFIC ST Census Tract:   45 Health Area:  2300
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11201 Community Board:   306
DOB Cross Street(s):   CLINTON STREET,    COURT STREET
Status:   E - ABANDONED 08/22/2025
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   12/15/2009 Job Start Date:   12/16/2009
Last Change:   08/22/2025 Job End Date:   12/21/2009
               COMPLETION FEE WAS BILLED
Appointment Status:   
Last Inspection By:   PETER GREENE       On     05/14/2010      
Field Disp:   A - OBJCTN ISSD: JOB COMPLETE
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012014 Licensee Name: JOSEPH ALOIA
Firm: 002078 Firm Name: ALL WAYS ELECTRIC CORP.W
Firm Phone: 800-924-9297  Firm Address: 112 WEST 34TH STREET FLR 17 NEWYORK NY 10120 

Other Licensees and Firms:
License # Licensee Name Firm # Firm Name Type
010813 ESPOSITO, RICHARD 002078 ALL WAYS ELECTRIC CORP.W RESPONSIBLE REP

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
9 - OTHER
Total Fee:  $55.00
Other Work:   REMOVE VIOLATION
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JOYCE RASKIN
Authorized Representative:  JOYCE RASKIN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 05/14/2010 Notice: 1 - FIRST NOTICE 05/14/2010
Power Issued: 05/14/2010 Response: F - FILED TO REMOVE OBJECTION 12/15/2009

Follow-Up: F - FILED TO REMOVE OBJECTION 12/15/2009
Contractor's Comments:  CLEAR VIOLATION ISSUED TO OWNER

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B321735
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/28/2009 11/02/2009 FMO W (5) (4)
INSPECTION COMMENTS: N
 
(2) 05/14/2010 05/14/2010 PGR A R E (15) (1) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B321735
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 29) OUTLET BOXES ARE NOT COVERED
PANEL COVER MISSING IN BASEMENT 314.25
RSLV 10/28/2009 10/28/2009 05/14/2010
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
WATER GROUND NOT PROPERLY TERMINATED 250.24
RSLV 10/28/2009 10/28/2009 05/14/2010
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
TRANSFORMER IN SERVICE AREA NOT GROUNDED 250.112
RSLV 10/28/2009 10/28/2009 05/14/2010
 
004 (999) OTHER
NEUTRAL BONDED AFTER SERVICE SWITCH IN BASEMENT 250.24A (5)
RSLV 10/28/2009 10/28/2009 05/14/2010
 
005 (999) OTHER
BSMT MAIN BREAKER NOT BOLTED IN 408.16F
OPEN 05/14/2010 05/14/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.