Electrical Application Details for App #: B320224
Premises: 112 LOUISIANA AVENUE BROOKLYN BIN: 3097176     Block: 4317   Lot: 28
   
Application Completed and Certified

Filed: 112 LOUISIANA AV Census Tract:   1098 Health Area:  7520
DEWITT AND LINDEN BLVD Admin Area:   B - BROOKLYN Inspection Area:   L
BROOKLYN, NY 11207 Community Board:   305
Special Place Name:   BETWEEN
DOB Cross Street(s):   LINDEN BOULEVARD,    DE WITT AVENUE
Status:   C - JOB IS SIGNED OFF 03/11/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  09/12/2009 11:53 AM
Application Entered:   09/12/2009 Job Start Date:   09/15/2009
Last Change:   03/11/2010 Job End Date:   02/28/2010
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     02/09/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011015 Licensee Name: ERROL G GLANVILLE
Firm: 002353 Firm Name: THROOP ELECTRIC CO., INC.
Firm Phone: 718-282-8201  Firm Address: 610 ROGERS AVENUE BROOKLYN NY 11225 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $86.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: THERESA JAQUES
Authorized Representative:  THERESA JAQUES
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  2  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 2 + New Meters 2 - Removed Meters 2 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/12/2009 Notice:  01/05/2010
Power Issued: 09/12/2009 Response: V - OBJ WAS REMOVED 01/25/2010

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B320224
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/30/2009 01/05/2010 MC2 V E (30) (6) Y
INSPECTION COMMENTS: P/U EXISTING BRANCH CIRCUIT WIRING DEFECTIVE AND DETERIATED
 
(2) 02/09/2010 02/17/2010 PAT C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B320224
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
COMBO S/S NEUTRAL BOTH PANELS NOT BONDED TO ENCLOSURE 250.10
RSLV 12/30/2009 12/30/2009 02/09/2010
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
OLD BR CKTS 14 GA WIRE ON 20 AMP C.B OVER FUSED
RSLV 12/30/2009 12/30/2009 02/09/2010
 
003 (999) OTHER
C.B NOT AS PER MFG LISTING 110.3
RSLV 12/30/2009 12/30/2009 02/09/2010
 
004 ( 62) ELECTRICAL PERMIT IS NOT CONSPICUOUSLY POSTED AT THE SITE
PANELS BOTH DIRECTORIES NOT PROVIDED
RSLV 12/30/2009 12/30/2009 02/09/2010
 
005 (999) OTHER
BOTH PANELS WIRE SMALLER THAN #4 AWG IN EMT REIDENTIFIED W/TAPE
RSLV 12/30/2009 12/30/2009 02/09/2010
 
006 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
MIGB NOT BONDED TO ENCLOSURE
RSLV 12/30/2009 12/30/2009 02/09/2010