Electrical Application Details for App #: B319945
Premises: 683 BARBEY STREET BROOKLYN BIN: 3398467     Block: 4091   Lot: 16
   
Application Completed and Certified

Filed: 679 NEW LOTS AV Census Tract:   1124 Health Area:  6420
1,2,3,4,5,6,7,R Admin Area:   B - BROOKLYN Inspection Area:   U
BROOKLYN, NY 11207 Community Board:   305
Related Job Number:    310210704
DOB Cross Street(s):   JEROME STREET,    JEROME STREET
Status:   C - JOB IS SIGNED OFF 11/24/2010
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   09/01/2009 Job Start Date:   09/15/2009
Last Change:   11/24/2010 Job End Date:   09/15/2010
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     10/19/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012116 Licensee Name: MARK REYES
Firm: 003819 Firm Name: GOTHAM TECHNICAL SERVICES
Firm Phone: 800-762-0240  Firm Address: 218-14 NORTHERN BLVD INC DBA GTS ELECTRICAL BAYSIDE NY 11361 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $4,510.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (1  Stores, 87 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: JACKSON BUILDERS
Authorized Representative:  XX XX
Relationship To Owner:   XX


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  1  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  87  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  4  
D. Over 250 MCM  8  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  87  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  8  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 87 #4-Wire 2 #10-Wire 2
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 09/01/2009 Notice: 1 - FIRST NOTICE 08/25/2010
Power Issued: 09/01/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B319945
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/24/2010 08/25/2010 NI1 A E (80) (2) Y
INSPECTION COMMENTS: N
 
(2) 10/19/2010 10/29/2010 PAT C R E (20) (0) Y
INSPECTION COMMENTS: -

OBJECTION FOR APPLICATION #: B319945
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
LINE AND LOAD IN THE SAME ENCLOSURE (230.7) 600A SERVICE SWITCH
RSLV 08/24/2010 08/24/2010 10/19/2010
 
002 (999) OTHER
FRONT ACCESS SWITCH IS MORE THAN 12" FROM REAR WALL (230.64.B.4)
RSLV 08/24/2010 08/24/2010 10/19/2010