BIS Menu  |  Plumb. Inspections  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B319523
Premises: 1322 AVENUE U BROOKLYN BIN: 3199489     Block: 7346   Lot: 9
   
Application Completed and Certified

Filed: 1322 AV U Census Tract:   582 Health Area:  8710
BASEMENT & 1ST FLOOR Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11229 Community Board:   315
DOB Cross Street(s):   EAST 13 STREET,    EAST 14 STREET
Status:   C - JOB IS SIGNED OFF 07/14/2010
Request Type:   P - PICK-UP eFiled:   YES
Application Entered:   04/05/2010 Job Start Date:   04/18/2010
Last Change:   07/14/2010 Job End Date:   04/30/2010
Appointment Status:   
Last Inspection By:   COHN, MARTIN       On     07/01/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010606 Licensee Name: MYRON COHEN
Firm: 003435 Firm Name: A.T. ELEC'L CONTR'G, INC
Firm Phone: 718-234-9250  Firm Address: 1561 64TH STREET BROOKLYN NY 11219 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $56.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: SOON LEE
Owner Business Name: BANK
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  #10/3 WIRE
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/14/2010 Notice:  08/19/2009
Power Issued: 07/14/2010 Response: F - FILED TO REMOVE OBJECTION 04/05/2010

Follow-Up: X - FILED APPL,NOW CLOSED 04/05/2010
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B319523
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/10/2009 08/19/2009 MC2 W (15) (6)
INSPECTION COMMENTS: NO FINAL INSPECTION
 
(2) 07/01/2010 07/14/2010 MC2 C R E (55) (0) Y
INSPECTION COMMENTS: P/U 2 SIGNS #3W VIOLATIONS REMOVED

OBJECTION FOR APPLICATION #: B319523
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 3) APPLICATION FOR CERTIFICATE OF ELECTRICAL INSPECTION NOT ON FILE
NO APPLICATION ON FILE WIRING IN BASEMENT A/C COMPRESSOR, FEEDERCONTROLS, MOTORS, BRANCH CIRCUITS
RSLV 08/10/2009 08/10/2009 07/01/2010
 
002 ( 53) GFCI HAS NOT BEEN PROVIDED
BASEMENT, RECEPT. OUTLET NOT GFIC PROTECTED
RSLV 08/10/2009 08/10/2009 07/01/2010
 
003 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
A/C COMPRESSOR DIS SWITCH NOT PROVIDED
RSLV 08/10/2009 08/10/2009 07/01/2010
 
004 ( 35) APPROVED OUTLETS HAVE NOT BEEN PROVIDED FOR AIR CONDITIONERS
SERVICE RECEPT OUTLET NOT PROVIDED AT A/C COMPRESSOR
RSLV 08/10/2009 08/10/2009 07/01/2010
 
005 ( 7) EMT IS NOT PROPERLY SUPPORTED (TYPE:EMT)
BASMT EMT NOT PROPERLY SUSPPORTED
RSLV 08/10/2009 08/10/2009 07/01/2010
 
006 ( 30) OUTLET BOXES ARE NOT SECURED
BSMENT CEILING BOXES NOT SUPPORTEDNOT FINAL INSPECTION
RSLV 08/10/2009 08/10/2009 07/01/2010