BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B318790
Premises: 2132 EAST 14 STREET BROOKLYN BIN: 3199498     Block: 7346   Lot: 20
   
Application Completed and Certified

Filed: 2132 E 14 ST Census Tract:   582 Health Area:  8710
BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11229 Community Board:   315
DOB Cross Street(s):   AVENUE U,    AVENUE V
Status:   C - JOB IS SIGNED OFF 04/08/2010
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/28/2009 Job Start Date:   07/24/2009
Last Change:   04/08/2010 Job End Date:   12/11/2009
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     03/29/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 012124 Licensee Name: AI FANG WU
Firm: 003828 Firm Name: KWONG MING ELECTRIC INC
Firm Phone: 718-266-2883  Firm Address: 2516 MCDONALD AVENUE BROOKLYN NY 11223 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $87.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   C - Three Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: MIKE KONG
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  4  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  1  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 4 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/28/2009 Notice: 1 - FIRST NOTICE 02/01/2010
Power Issued: 07/28/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B318790
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 11/04/2009 11/09/2009 JMZ A E (45) (1) Y
INSPECTION COMMENTS: N
 
(2) 12/10/2009 12/11/2009 MC2 V R E (30) (4) Y
INSPECTION COMMENTS: NEW VIOLATION EXISTING
 
(3) 01/25/2010 02/01/2010 MC2 V R E (45) (2) Y
INSPECTION COMMENTS: NEW VIOLATION EXISTING
 
(4) 03/29/2010 04/08/2010 PAT C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B318790
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
HI/LO VOLTAGE SERVICE TROUGH
RSLV 11/04/2009 11/04/2009 12/10/2009
 
002 (999) OTHER
S.E CONDUIT WITH HOLLOW OF FRAME BLDG 230.43E
RSLV 12/10/2009 12/10/2009 01/25/2010
 
003 (999) OTHER
METAL STUD ZIP SCREWED INTO PANELS THROUGH NOT PERMITTED
RSLV 12/10/2009 12/10/2009 01/25/2010
 
004 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
WATER METER JUMPER NOT PROVIDED 250
RSLV 12/10/2009 12/10/2009 01/25/2010
 
005 (999) OTHER
SUPPLEMENTAL BOXES AND CONDULETS SHALL BE ACCESSIBLE NOT PROVIDED(S.E)
RSLV 12/10/2009 12/10/2009 01/25/2010
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
S.E CONDUIT SET SCREW FITTINGS USED NOT WEATHER PROOF 110.2
RSLV 01/25/2010 01/25/2010 03/29/2010
 
007 (999) OTHER
INSIDE AT SERVICE EQUIPT WATER LINES IN DEDICATED EQUIPT SPACE 110.26F
RSLV 01/25/2010 01/25/2010 03/29/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.