BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B317269
Premises: 188 EMPIRE BOULEVARD BROOKLYN BIN: 3034760     Block: 1314   Lot: 21
   
Application Completed and Certified

Filed: 200 EMPIRE BLVD Census Tract:   327 Health Area:  4800
CELLAR, 1-3, ROOF Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11225 Community Board:   309
Related Job Number:    310016684
DOB Cross Street(s):   BEDFORD AVENUE,    ROGERS AVENUE
Status:   C - JOB IS SIGNED OFF 02/11/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  06/11/2009 10:22 AM
Application Entered:   06/11/2009 Job Start Date:   06/11/2009
Last Change:   02/11/2010 Job End Date:   09/11/2009
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     02/02/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 010659 Licensee Name: PETER J GIOELLO
Firm: 000117 Firm Name: AMBER LITE ELECTRIC CORP.
Firm Phone: 718-605-5200  Firm Address: 441 WILD AVE 2ND FLOOR STATEN ISLAND NY 10314 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $1,920.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Other
Store / Other:   STORAGE FACILITY
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: NEIL SIMON
Owner Business Name: WOODMONT DEVELOPMENT CO.
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  3 - 400 AMP
D. 601 Up to 1200 AMPS  1  1 - 800 AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  2  3 - #3'S
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  6  4 - 3/0
D. Over 250 MCM  5  5 SETS 600 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  (1)100A12/24(1)100A30CKT
C. 3 Phase Up to 225 AMPS  6  (6) 200 AMP 42 CKT
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    66  100    20  60             
001    58  21    58  124         
002    136  27    18  136             
003    128  15    12  126             
ROF            58         
Buildings Total 388  167    55  380     182           
Total Units : 1172 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 1
Existing Meters 2 + New Meters 1 - Removed Meters 1 = Total Meters 2

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 06/11/2009 Notice:  12/07/2009
Power Issued: 06/11/2009 Response: W - OBJ TO BE REMOVED 01/04/2010

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B317269
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/03/2009 12/07/2009 JMZ A E (105) (7) Y
INSPECTION COMMENTS: N
 
(2) 02/02/2010 02/11/2010 PAT C R E (45) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B317269
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
GROUND SERVICE TO BUILDING STTEL
RSLV 12/03/2009 12/03/2009 02/02/2010
 
002 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
REMOVE ALL TEMP WIRING
RSLV 12/03/2009 12/03/2009 02/02/2010
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ROOF A/C TECK SCREW USED FOR GROUNDING
RSLV 12/03/2009 12/03/2009 02/02/2010
 
004 ( 42) BUSHINGS ARE MISSING OR LOOSE
ROOF A/C #4 AND LARGER NEED BUSHING
RSLV 12/03/2009 12/03/2009 02/02/2010
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BOND ALL RECEPTACLES
RSLV 12/03/2009 12/03/2009 02/02/2010
 
006 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
MARK SERVICE SWITCHES
RSLV 12/03/2009 12/03/2009 02/02/2010
 
007 ( 45) FIXTURE NOT INSTALLED IN AN APPROVED MANNER
OFFICE TRACK LIGHT SUPPORT BOX
RSLV 12/03/2009 12/03/2009 02/02/2010



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.