BIS Menu  |  After Hours Variance Permits  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B316032
Premises: 172 EMPIRE BOULEVARD BROOKLYN BIN: 3034759     Block: 1314   Lot: 15
   
Application Completed and Certified

Filed: 172 EMPIRE BLVD. Census Tract:   327 Health Area:  4800
ENTIRE NEW BLDG. Admin Area:   B - BROOKLYN Inspection Area:   G
BROOKLYN, NY 11225 Community Board:   309
DOB Cross Street(s):   BEDFORD AVENUE,    ROGERS AVENUE
Status:   C - JOB IS SIGNED OFF 02/16/2012
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  05/05/2009 9:44 AM
Application Entered:   05/05/2009 Job Start Date:   05/10/2009
Last Change:   02/16/2012 Job End Date:   05/01/2010
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     12/22/2011      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011212 Licensee Name: PAUL LEFKOWITZ
Firm: 001756 Firm Name: BLZ ELECTRIC INC.
Firm Phone: 718-677-5900  Firm Address: 1243 EAST 15TH STREET BROOKLYN NY 11230 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
7 - HVAC WIRING
Total Fee:  $925.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   O - Office Bldg
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup:
Owner Business Name: A W S
Authorized Representative:  N STERN
Relationship To Owner:   CONT


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  3  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  3  
D. Over 250 MCM  3  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  3  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
GND    20  20    10  20             
001    20  20    10  20             
002    20  20    10  20             
ROF              40         
Buildings Total 60  60    30  60     40           
Total Units : 250 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 0 #10-Wire 3
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 05/05/2009 Notice: 1 - FIRST NOTICE 08/08/2011
Power Issued: 05/05/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B316032
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 08/04/2011 08/08/2011 JMZ A E (90) (11) Y
INSPECTION COMMENTS: N
 
(2) 10/19/2011 10/24/2011 JMZ J Y E (45) (0) Y
INSPECTION COMMENTS: N
 
(3) 12/22/2011 12/28/2011 PAT C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B316032
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
(3) TAP END GROUND EACH SERVICE SWITCH
RSLV 08/04/2011 10/19/2011 12/22/2011
 
002 ( 1) SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER
2ND AND 3RD FLOOR SERVICE SWITCH BOND NEUTRAL
RSLV 08/04/2011 08/04/2011 10/19/2011
 
003 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUND ALL FEED BASEMENT PANELS
RSLV 08/04/2011 08/04/2011 10/19/2011
 
004 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
BASEMENT GROUND FLOOR PANEL WHITE USE AS UNGROUNDED CONDUCTOR
RSLV 08/04/2011 08/04/2011 10/19/2011
 
005 ( 40) LOCKNUTS ARE MISSING OR LOOSE
BASEMENT GROUND FLOOR PANEL BUSHING MISSING
RSLV 08/04/2011 08/04/2011 10/19/2011
 
006 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
GROUND FLOOR STORE PANEL GROUNDS ON NEUTRAL
RSLV 08/04/2011 08/04/2011 10/19/2011
 
007 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ELEVATOR MOTOR ROOM LIGHT DISCONNECT SWITCH GROUND ON NEUTRAL
RSLV 08/04/2011 08/04/2011 10/19/2011
 
008 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
LARGE ROOF A/C GROUND NOT SUFFICIENT
RSLV 08/04/2011 08/04/2011 10/19/2011
 
009 ( 16) DEFECTIVE LIGHTING FIXTURES ARE IN USE
EMERGENCY LIGHT DEFECTIVE 3RD FLOOR STAIRS NEAR ELEVATOR
RSLV 08/04/2011 08/04/2011 10/19/2011
 
010 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
3RD FLOOR PANEL FEED GROUND NOT TERMINATED AND 2ND FLOOR
RSLV 08/04/2011 08/04/2011 10/19/2011
 
011 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NO PANEL DIRCETORY
RSLV 08/04/2011 08/04/2011 10/19/2011



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.