| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
3 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
3 |
|
| D. Over 250 MCM |
3 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
3 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY (3) TAP END GROUND EACH SERVICE SWITCH |
RSLV |
08/04/2011 |
10/19/2011 |
12/22/2011 |
| |
| 002 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER 2ND AND 3RD FLOOR SERVICE SWITCH BOND NEUTRAL |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 003 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED GROUND ALL FEED BASEMENT PANELS |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 004 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED BASEMENT GROUND FLOOR PANEL WHITE USE AS UNGROUNDED CONDUCTOR |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 005 |
( 40) |
LOCKNUTS ARE MISSING OR LOOSE BASEMENT GROUND FLOOR PANEL BUSHING MISSING |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 006 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED GROUND FLOOR STORE PANEL GROUNDS ON NEUTRAL |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 007 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED ELEVATOR MOTOR ROOM LIGHT DISCONNECT SWITCH GROUND ON NEUTRAL |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 008 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED LARGE ROOF A/C GROUND NOT SUFFICIENT |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 009 |
( 16) |
DEFECTIVE LIGHTING FIXTURES ARE IN USE EMERGENCY LIGHT DEFECTIVE 3RD FLOOR STAIRS NEAR ELEVATOR |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 010 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED 3RD FLOOR PANEL FEED GROUND NOT TERMINATED AND 2ND FLOOR |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |
| |
| 011 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY NO PANEL DIRCETORY |
RSLV |
08/04/2011 |
08/04/2011 |
10/19/2011 |