| BUILDING OVERVIEW |
Are Feeders Being Installed? : No |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
0 |
|
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 19) |
DEFECTIVE WIRING IS IN USE RANGE HOOD OPEN WIRE B, 1 AND 2 FLRS |
RSLV |
05/11/2009 |
05/11/2009 |
09/23/2009 |
| |
| 002 |
( 19) |
DEFECTIVE WIRING IS IN USE BATHROOM GFI ABOVE SINK AT 1ST AND 2ND FLRS |
RSLV |
05/11/2009 |
05/11/2009 |
09/23/2009 |
| |
| 003 |
( 53) |
GFCI HAS NOT BEEN PROVIDED OUTSIDE FRONT |
RSLV |
05/11/2009 |
05/11/2009 |
09/23/2009 |
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED BASEMENT BY STOVE |
RSLV |
05/11/2009 |
05/11/2009 |
09/23/2009 |
| |
| 005 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER KITCHEN COUNTER TOP NO TWO CIRCUITS AND FIXTURES ON WITH COUNTER TOPAT BASEMENT 1ST AND 2ND FLRS |
RSLV |
05/11/2009 |
05/11/2009 |
09/23/2009 |
| |
| 006 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED NO ARCH FAULT FOR LIGHTS , OUTLETS, A/C AT ALL BEDROOMS BASEMENT -2ND FLRS |
RSLV |
05/11/2009 |
05/11/2009 |
09/23/2009 |