Electrical Application Details for App #: B313782
Premises: 2973 OCEAN AVENUE BROOKLYN BIN: 3204407     Block: 7441   Lot: 240
   
Application Completed and Certified

Filed: 2973 OCEAN AV Census Tract:   594.01 Health Area:  8722
BAS , 1ST ,2ND , 3RD FLOORS Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11235 Community Board:   315
DOB Cross Street(s):   AVENUE Y,    AVENUE Z
Status:   C - JOB IS SIGNED OFF 10/13/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/23/2009 5:13 PM
Application Entered:   02/23/2009 Job Start Date:   02/25/2010
Last Change:   10/13/2009 Job End Date:   03/25/2010
Appointment Status:   
Last Inspection By:   COHN, MARTIN       On     10/08/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011267 Licensee Name: ALEXANDER ABRAMOVICH
Firm: 002666 Firm Name: INTEGRAL ELECL PWR & CNTR
Firm Phone: 212-645-5528  Firm Address: 307 7TH AVENUE,SUITE 301 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $341.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (1  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: IGOR KISIN
Owner Business Name: PRIME CORNER LLC
Authorized Representative:  IGOR KISIN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS                 
001      10  10             
002      24  12             
003      24  12             
Buildings Total 18    62  19  40                
Total Units : 139 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 1 #10-Wire 0
Existing Meters 1 + New Meters 4 - Removed Meters 1 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/23/2009 Notice: 1 - FIRST NOTICE 09/08/2009
Power Issued: 02/23/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  BAS , 1ST FLOOR - COMMERCIAL (FUTURE) ,2ND , 3RD FLOORS-TWORESIDENTIAL APARTMENTS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B313782
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/01/2009 09/08/2009 MC2 V E (40) (7) Y
INSPECTION COMMENTS: N
 
(2) 10/08/2009 10/13/2009 MC2 C R E (30) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B313782
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT PLP C.B. COMBO PANEL SERVICE SWITCH NOT PROVIDED 230.91
RSLV 09/01/2009 09/01/2009 10/08/2009
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BSMT PLP NEUTRAL NOT BONDED TO ENCLOSURE 250.24 A5
RSLV 09/01/2009 09/01/2009 10/08/2009
 
003 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
2ND 3RD FL APTS ALL BEDROOMS AFCI PROTECTION FOR A/C NOT PROVIDED210.12B
RSLV 09/01/2009 09/01/2009 10/08/2009
 
004 (999) OTHER
ENTIRE BOXES NOT FLUSH TO FINISH WALL COLLARS NEEDED 314.20
RSLV 09/01/2009 09/01/2009 10/08/2009
 
005 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ENTIRE RECPT OUTLETS NOT GROUNDED TO BOX 250.146
RSLV 09/01/2009 09/01/2009 10/08/2009
 
006 (999) OTHER
BSMT BOILER ROOM HI LOW IN SAME RACEWAY 725.51/55
RSLV 09/01/2009 09/01/2009 10/08/2009
 
007 ( 62) ELECTRICAL PERMIT IS NOT CONSPICUOUSLY POSTED AT THE SITE
GND FL PERMIT TO PERFORM ELECTRICAL WORK NOT DISPLAYED 27.3018B
RSLV 09/01/2009 09/01/2009 10/08/2009