BIS Menu  |  Electrical Inspection Work Order   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B313764
Premises: 2971 OCEAN AVENUE BROOKLYN BIN: 3204408     Block: 7441   Lot: 241
   
Application Completed and Certified

Filed: 2971 OCEAN AV Census Tract:   594.01 Health Area:  8722
BAS , 1ST , 2ND , 3RD FLOORS Admin Area:   B - BROOKLYN Inspection Area:   P
BROOKLYN, NY 11235 Community Board:   315
DOB Cross Street(s):   AVENUE Y,    AVENUE Z
Status:   C - JOB IS SIGNED OFF 10/13/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/23/2009 2:34 PM
Application Entered:   02/23/2009 Job Start Date:   02/25/2009
Last Change:   10/13/2009 Job End Date:   03/25/2010
Appointment Status:   
Last Inspection By:   COHN, MARTIN       On     10/08/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011267 Licensee Name: ALEXANDER ABRAMOVICH
Firm: 002666 Firm Name: INTEGRAL ELECL PWR & CNTR
Firm Phone: 212-645-5528  Firm Address: 307 7TH AVENUE,SUITE 301 NEW YORK NY 10001 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $343.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (1  Stores, 2 Apartments)
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: IGOR KISIN
Owner Business Name: PRIME CORNER LLC
Authorized Representative:  IGOR KISIN
Relationship To Owner:   OWNER


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  
B. Over #2 to 1/0  1  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  1  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  2  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
BAS             
001      10  10             
002      24  12             
003      24  12             
Buildings Total 18    62  19  40              
Total Units : 147 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 1 #10-Wire 0
Existing Meters 2 + New Meters 4 - Removed Meters 2 = Total Meters 4

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/23/2009 Notice: 1 - FIRST NOTICE 09/08/2009
Power Issued: 02/23/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  BAS , 1ST FLOOR - COMMERSIAL (FUTURE) 2ND , 3RD FLOORS - TWO RESIDENTIAL APARTMENTS

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B313764
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 09/01/2009 09/08/2009 MC2 V E (30) (7) Y
INSPECTION COMMENTS: N
 
(2) 10/08/2009 10/13/2009 MC2 C R E (30) (0) Y
INSPECTION COMMENTS: VIOLATION REMOVED

OBJECTION FOR APPLICATION #: B313764
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
BSMT PLP COMBO PANEL SER SWITCH NOT PROVIDED 230.91
RSLV 09/01/2009 09/01/2009 10/08/2009
 
002 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
PLP PANEL NEUTRAL NOT BONDED TO ENCLOSURE 250.5
RSLV 09/01/2009 09/01/2009 10/08/2009
 
003 (999) OTHER
ENTIRE BOXES NOT FLUSH TO FINISH SURFACE COLLARS NEEDED 314.20
RSLV 09/01/2009 09/01/2009 10/08/2009
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
ENTIRE RECEPT OUTLETS NOT GROUNDED TO BOX 250.146
RSLV 09/01/2009 09/01/2009 10/08/2009
 
005 ( 59) AFCI PROTECTION HAS NOT BEEN PROVIDED
2.3.FL AFIC PROTECTION FOR A/C RECPT IN BEDROOMS NOT PROVIDED210.82B
RSLV 09/01/2009 09/01/2009 10/08/2009
 
006 (999) OTHER
BSMT BOILER ROOM HI AND LO IN SAME RACEWAY 725.54
RSLV 09/01/2009 09/01/2009 10/08/2009
 
007 ( 62) ELECTRICAL PERMIT IS NOT CONSPICUOUSLY POSTED AT THE SITE
GND FL ELECTRICAL PERMIT NOT POSTED 27.3018B
RSLV 09/01/2009 09/01/2009 10/08/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Inspection Work Order