Electrical Application Details for App #: B313460
Premises: 286 STANHOPE STREET BROOKLYN BIN: 3074527     Block: 3270   Lot: 10
   
Application Completed and Certified

Filed: 286 STANHOPE ST Census Tract:   443 Health Area:  3300
CELLAR THRU 5TH FLOOR Admin Area:   B - BROOKLYN Inspection Area:   E
BROOKLYN, NY 11237 Community Board:   304
Related Job Number:    310026682
DOB Cross Street(s):   IRVING AVENUE,    WYCKOFF AVENUE
Status:   C - JOB IS SIGNED OFF 03/19/2010
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  02/12/2009 12:06 PM
Application Entered:   02/12/2009 Job Start Date:   02/12/2009
Last Change:   03/19/2010 Job End Date:   12/30/2010
Appointment Status:   
Last Inspection By:   MOSES, FITZROY       On     03/15/2010      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011769 Licensee Name: ZHENG LI
Firm: 003451 Firm Name: KJK ELECTRIC INC
Firm Phone: 917-682-3886  Firm Address: 79 BRIDGEWATER STREET BROOKLYN NY 11222 

Work Started or Filed by Others: NO
Work Category:   N - NEW BUILDING Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $2,256.25
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   YES
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   L - Five Or More Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: JACOB SACKS
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  1  100 AMP C/B SWITCH
B. 101 Up to 200 AMPS  1  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  3  800 AMP , 1200 AMP
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  23  #2 AWG WIRE
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  6  500 MCM
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  28  20 POSITION PANEL
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  2  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
CEL    19                 
001    16                 
002  21  81  12  18               
003  21  81  12  18               
004  21  81  12  18               
005  18  61  10  15               
Buildings Total 116  317  46  84                  
Total Units : 563 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 28 #4-Wire 0 #10-Wire 2
Existing Meters 0 + New Meters 30 - Removed Meters 0 = Total Meters 30

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 02/12/2009 Notice: 1 - FIRST NOTICE 01/25/2010
Power Issued: 02/12/2009 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  NEW BUILDING OBTAIN C/O

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B313460
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 12/04/2009 12/04/2009 FMO V E (150) (5) Y
INSPECTION COMMENTS: N
 
(2) 01/19/2010 01/25/2010 DEX V Y E (105) (0) Y
INSPECTION COMMENTS: NOT A FINAL INSPECTION
 
(3) 01/20/2010 01/25/2010 DEX V Y E (105) (5) Y
INSPECTION COMMENTS: NOT A FINAL INSPECTION
 
(4) 03/15/2010 03/19/2010 FMO C R E (1) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B313460
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 (999) OTHER
A BASEMENT WORK SPACE NOT PROVIDED FOR 1200 AMP FIRE PUMP SERVICESWITCH 110.26
RSLV 12/04/2009 12/04/2009 01/19/2010
 
002 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
NEUTRALS SPLICED TOGETHER IN 400 AMP PANELS 110.2
RSLV 12/04/2009 12/04/2009 01/19/2010
 
003 (999) OTHER
E LIMITED FIRE PUMP NOT AT 150 0/0 695
RSLV 12/04/2009 01/19/2010 01/20/2010
 
004 (999) OTHER
B 800 AMP SERVICE FUSES NOT CORDINATED 240.12
RSLV 12/04/2009 01/19/2010 01/20/2010
 
005 (999) OTHER
D BATHROOM OUTLETS MORE THAN 36 FROM ADJACENT WALL
RSLV 12/04/2009 12/04/2009 01/19/2010
 
006 (999) OTHER
SERVICE EQUIPMENT NOT ACCESSIBLE 3FT MIN CLEARANCE 1600 SERVICESWITCH 230.70
RSLV 01/20/2010 01/20/2010 03/15/2010
 
007 (999) OTHER
NEED PANIC BAR RELEASE OVER 1200 AMP SERVICE 110.26.02
RSLV 01/20/2010 01/20/2010 03/15/2010
 
008 (999) OTHER
JOCKEY PUMP FEED IN FIRE PUMP SWITCH 695.4B2(3)
RSLV 01/20/2010 01/20/2010 03/15/2010
 
009 (999) OTHER
FUSE CAST OUT IN PUMP SERVICE SWITCH 695.4B2(3)
RSLV 01/20/2010 01/20/2010 03/15/2010
 
010 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
800 AMP FUSED AT 3 SETS OF 250 MCM
RSLV 01/20/2010 01/20/2010 03/15/2010