| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
1 |
100 AMP C/B SWITCH |
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
3 |
800 AMP , 1200 AMP |
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
23 |
#2 AWG WIRE |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
6 |
500 MCM |
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
28 |
20 POSITION PANEL |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
2 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
(999) |
OTHER A BASEMENT WORK SPACE NOT PROVIDED FOR 1200 AMP FIRE PUMP SERVICESWITCH 110.26 |
RSLV |
12/04/2009 |
12/04/2009 |
01/19/2010 |
| |
| 002 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED NEUTRALS SPLICED TOGETHER IN 400 AMP PANELS 110.2 |
RSLV |
12/04/2009 |
12/04/2009 |
01/19/2010 |
| |
| 003 |
(999) |
OTHER E LIMITED FIRE PUMP NOT AT 150 0/0 695 |
RSLV |
12/04/2009 |
01/19/2010 |
01/20/2010 |
| |
| 004 |
(999) |
OTHER B 800 AMP SERVICE FUSES NOT CORDINATED 240.12 |
RSLV |
12/04/2009 |
01/19/2010 |
01/20/2010 |
| |
| 005 |
(999) |
OTHER D BATHROOM OUTLETS MORE THAN 36 FROM ADJACENT WALL |
RSLV |
12/04/2009 |
12/04/2009 |
01/19/2010 |
| |
| 006 |
(999) |
OTHER SERVICE EQUIPMENT NOT ACCESSIBLE 3FT MIN CLEARANCE 1600 SERVICESWITCH 230.70 |
RSLV |
01/20/2010 |
01/20/2010 |
03/15/2010 |
| |
| 007 |
(999) |
OTHER NEED PANIC BAR RELEASE OVER 1200 AMP SERVICE 110.26.02 |
RSLV |
01/20/2010 |
01/20/2010 |
03/15/2010 |
| |
| 008 |
(999) |
OTHER JOCKEY PUMP FEED IN FIRE PUMP SWITCH 695.4B2(3) |
RSLV |
01/20/2010 |
01/20/2010 |
03/15/2010 |
| |
| 009 |
(999) |
OTHER FUSE CAST OUT IN PUMP SERVICE SWITCH 695.4B2(3) |
RSLV |
01/20/2010 |
01/20/2010 |
03/15/2010 |
| |
| 010 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE 800 AMP FUSED AT 3 SETS OF 250 MCM |
RSLV |
01/20/2010 |
01/20/2010 |
03/15/2010 |