| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
3 |
100AMP |
| B. 101 Up to 200 AMPS |
0 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
5 |
#2AWG |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
0 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
2 |
|
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 1) |
SERVICE EQUIPMENT ENCLOSURES ARE NOT BONDED TOGETHER BSMT S.E. BETWEEN TROFF AND METER CONDUIT NOT PROPERLY SET 250.92 |
RSLV |
04/30/2009 |
06/08/2009 |
07/16/2009 |
| |
| 002 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY BSMT AT WATER MAIN STRANDED CONDUCTOR LUG NOT PROVIDED 250.24 |
RSLV |
04/30/2009 |
06/08/2009 |
07/16/2009 |
| |
| 003 |
(999) |
OTHER BSMT PLP PANEL SUPPLING OTHER BRANCH CIRCUIT 210.25 |
RSLV |
04/30/2009 |
06/08/2009 |
07/16/2009 |
| |
| 004 |
( 53) |
GFCI HAS NOT BEEN PROVIDED BSMT BATHROOM GFIC RECPT NOT PROVIDED 210.8 |
RSLV |
04/30/2009 |
06/08/2009 |
07/16/2009 |
| |
| 005 |
( 46) |
PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY ENTIRE PANELS ALL APTS DIRECTORY NOT PROVIDED 408.4 |
RSLV |
04/30/2009 |
06/08/2009 |
07/16/2009 |
| |
| 006 |
(999) |
OTHER BRANCH CIRCUIT REQUIRED FOR GFIC RECPT 210.12 |
RSLV |
04/30/2009 |
06/08/2009 |
07/16/2009 |
| |
| 007 |
(999) |
OTHER APT PANELS C.B NOT AS PER MFG LISTING 110.3 |
RSLV |
04/30/2009 |
06/08/2009 |
07/16/2009 |
| |
| 008 |
( 62) |
ELECTRICAL PERMIT IS NOT CONSPICUOUSLY POSTED AT THE SITE OUTSIDE PERMIT TO PERFORM ELECTRICAL WORK NOT POSTED 27-3018B |
RSLV |
04/30/2009 |
06/08/2009 |
07/16/2009 |