BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B311826
Premises: 75 COFFEY STREET BROOKLYN BIN: 3008813     Block: 598   Lot: 25
   
Application Completed and Certified

Filed: 75 COFFEY ST Census Tract:   57 Health Area:  4100
OUTDOORS AND PANELS INDOORS Admin Area:   B - BROOKLYN Inspection Area:   C
BROOKLYN, NY 11231 Community Board:   306
Special Place Name:   REDHOOK
DOB Cross Street(s):   RICHARDS STREET,    VAN BRUNT STREET
Status:   C - JOB IS SIGNED OFF 06/19/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  12/12/2008 3:23 PM
Application Entered:   12/12/2008 Job Start Date:   12/25/2008
Last Change:   06/19/2009 Job End Date:   01/25/2009
Appointment Status:   
Last Inspection By:   THOMAS, PATRICIA       On     04/22/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011917 Licensee Name: ALTAF H SYED-NAQVI
Firm: 003528 Firm Name: ALSON ELEC'L CONTR. INC
Firm Phone: 718-435-1677  Firm Address: 1253 ROCKAWAY AVENUE BROOKLYN NY 11236 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $139.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: FRED W PILS
Owner Business Name: RESIDENTIAL
Authorized Representative:  ABED BENAMOR
Relationship To Owner:   CONTRACTOR


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  M/B
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  3  1 SET OF 3WIRE THHN CU.
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  2  20 CKT. (110-220V) EACH
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 3 #4-Wire 0 #10-Wire 0
Existing Meters 3 + New Meters 3 - Removed Meters 3 = Total Meters 3

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 12/12/2008 Notice: 1 - FIRST NOTICE 01/23/2009
Power Issued: 12/12/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  INSTALLING 3 GANG METER PAN, 2 M/B, 3 PANELS.

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B311826
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 01/20/2009 01/23/2009 FMO A E (45) (3) Y
INSPECTION COMMENTS: N
 
(2) 03/02/2009 04/01/2009 FMO J Y (45) (0) Y
INSPECTION COMMENTS: N
 
(3) 04/22/2009 04/28/2009 PAT C R (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B311826
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTDOOR SERVICE ENTRANCE CONNECTORS NOT SUITABLE FOR PURPOSEINTENDED 110.2
RSLV 01/20/2009 01/20/2009 03/02/2009
 
002 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
GR FL FEEDERS TO APTS FUSED AT 90 AMPS 240.3
RSLV 01/20/2009 03/02/2009 04/22/2009
 
003 (999) OTHER
GR FL NO ILLUMINATION PROVIDED AT SERVICE 110.26D
RSLV 01/20/2009 03/02/2009 04/22/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back