BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
Building Overview Work Items |
QUANTITY |
DESCRIPTION |
SERVICE SWITCHES |
|
A. Up to 100 AMPS |
3 |
|
B. 101 Up to 200 AMPS |
0 |
|
C. 201 Up to 600 AMPS |
0 |
|
D. 601 Up to 1200 AMPS |
0 |
|
E. Over 1200 AMPS |
0 |
|
SER. ENT. & FDR COND (EACH SET) |
|
A. Up to #2 CONDUCTOR |
0 |
|
B. Over #2 to 1/0 |
0 |
|
C. Over 1/0 to 250 MCM |
1 |
|
D. Over 250 MCM |
0 |
|
PANELS |
|
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
0 |
|
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
C. 3 Phase Up to 225 AMPS |
0 |
|
D. 3 Phase Over 225 AMPS |
0 |
|
ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
B. Each Additional 10 Floors Or Less |
0 |
|
BOILER CONTROLS |
0 |
|
OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
|
001 |
( 22) |
FIXED EQUIPMENT IS NOT PROPERLY GROUNDED BSMT PLP PANEL COMBO S/S NEUTRAL NOT BONDED TO ENCLOSURE |
RSLV |
10/08/2009 |
10/08/2009 |
04/27/2010 |
|
002 |
(999) |
OTHER BSMT PLP METER USED FOR BSMT APT NOT FOR COMM AREA 27.3018B |
RSLV |
10/08/2009 |
10/08/2009 |
04/27/2010 |
|
003 |
( 24) |
ARMORED CABLES ARE NOT PROPERLY SECURED BSMT BOILER RM ARMORED CABLES HANGING NOT SUPPORTED |
RSLV |
10/08/2009 |
10/08/2009 |
04/27/2010 |
|
004 |
( 14) |
CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE BSMT ALL PANELS 20.C.B ON 14 GA WIRE |
RSLV |
10/08/2009 |
10/08/2009 |
04/27/2010 |
|
005 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY OUTSIDE GROUND TO DRIVEN ROD NOT CONTINOUS |
RSLV |
10/08/2009 |
10/08/2009 |
04/27/2010 |
|
006 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED OUTSIDE NIPPLE BETWEEN METERS NOT MADE WEATHER PROOF 110.2A |
RSLV |
10/08/2009 |
10/08/2009 |
04/27/2010 |
|
007 |
(999) |
OTHER OUTDOOR - NO HUB PROVIDED ON TOP OF END LINE BOX AND WIREWAY 321.2A |
RSLV |
04/27/2010 |
04/27/2010 |
09/09/2010 |
|
008 |
(999) |
OTHER BASEMENT PLP METER USED FOR BASEMENT APARTMENT AREA NOT FOR COMMONAREA 27.3018B |
OPEN |
04/27/2010 |
09/09/2010 |
|
|
009 |
( 5) |
SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY OUTSIDE GROUND DRIVEN ROD NOT CONTINUOUS |
OPEN |
04/27/2010 |
09/09/2010 |
|
|
010 |
( 56) |
ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED OUTSIDE NIPPLE BETWEEN METERS NOT MADE WATERPROOF 110.2A |
RSLV |
04/27/2010 |
04/27/2010 |
09/09/2010 |