Electrical Application Details for App #: B311385
Premises: 253 EXETER STREET BROOKLYN BIN: 3246334     Block: 8743   Lot: 26
  Printable (PDF) version of this Permit  

Filed: 253 EXETER ST Census Tract:   616 Health Area:  9120
OUTSIDE,BASEMENT Admin Area:   B - BROOKLYN Inspection Area:   R
BROOKLYN, NY 11235 Community Board:   315
DOB Cross Street(s):   ORIENTAL BOULEVARD,    DEAD END
Status:   I - AWAITING INSPECTION REQUEST
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   12/02/2008 Job Start Date:   11/27/2008
Last Change:   09/13/2010 Job End Date:   12/09/2008
Appointment Status:   
Last Inspection By:   JAMES CLANCY       On     09/09/2010      
Field Disp:   J - JOB IN PROGRESS
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  Y - PARTLY REMOVED

License #: 010133 Licensee Name: JOHN MUSTARO
Firm: 001167 Firm Name: POLYPHASE ELEC'L CONTR'S.
Firm Phone: 718-449-1003  Firm Address: 2201 NEPTUNE AVENUE BROOKLYN NY 11224 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $109.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   B - Two Family
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: VJACSESZLAV DIMONT
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  1  
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total                         
Total Units : 0 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 2 #4-Wire 0 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag: V - OBJECTION(S) EXIST
Power Requested: 12/02/2008 Notice:  05/03/2010
Power Issued: 12/02/2008 Response: W - OBJ TO BE REMOVED 05/14/2010

Follow-Up:
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B311385
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 10/08/2009 10/13/2009 MC2 V E (45) (6) Y
INSPECTION COMMENTS: N
 
(2) 12/15/2009 12/21/2009 MC2 N (10) (0) Y
INSPECTION COMMENTS: MET CONTRACTOR OWNER NO SHOW NO ACCESS
 
(3) 04/27/2010 05/03/2010 PAT A R E (40) (4) Y
INSPECTION COMMENTS: #99, #5 AND #56 TO REMAIN
 
(4) 09/09/2010 09/13/2010 JMZ J Y (30) (0) Y
INSPECTION COMMENTS: NO ACCESS , CONTRACTOR NO SHOW,

OBJECTION FOR APPLICATION #: B311385
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
BSMT PLP PANEL COMBO S/S NEUTRAL NOT BONDED TO ENCLOSURE
RSLV 10/08/2009 10/08/2009 04/27/2010
 
002 (999) OTHER
BSMT PLP METER USED FOR BSMT APT NOT FOR COMM AREA 27.3018B
RSLV 10/08/2009 10/08/2009 04/27/2010
 
003 ( 24) ARMORED CABLES ARE NOT PROPERLY SECURED
BSMT BOILER RM ARMORED CABLES HANGING NOT SUPPORTED
RSLV 10/08/2009 10/08/2009 04/27/2010
 
004 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
BSMT ALL PANELS 20.C.B ON 14 GA WIRE
RSLV 10/08/2009 10/08/2009 04/27/2010
 
005 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
OUTSIDE GROUND TO DRIVEN ROD NOT CONTINOUS
RSLV 10/08/2009 10/08/2009 04/27/2010
 
006 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTSIDE NIPPLE BETWEEN METERS NOT MADE WEATHER PROOF 110.2A
RSLV 10/08/2009 10/08/2009 04/27/2010
 
007 (999) OTHER
OUTDOOR - NO HUB PROVIDED ON TOP OF END LINE BOX AND WIREWAY 321.2A
RSLV 04/27/2010 04/27/2010 09/09/2010
 
008 (999) OTHER
BASEMENT PLP METER USED FOR BASEMENT APARTMENT AREA NOT FOR COMMONAREA 27.3018B
OPEN 04/27/2010 09/09/2010
 
009 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
OUTSIDE GROUND DRIVEN ROD NOT CONTINUOUS
OPEN 04/27/2010 09/09/2010
 
010 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
OUTSIDE NIPPLE BETWEEN METERS NOT MADE WATERPROOF 110.2A
RSLV 04/27/2010 04/27/2010 09/09/2010