BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B310768
Premises: 164 STEWART AVENUE BROOKLYN BIN: 3258606     Block: 2964   Lot: 54
   
Application Completed and Certified

Filed: 164 STEWART AV Census Tract:   455 Health Area:  0900
1ST FL Admin Area:   B - BROOKLYN Inspection Area:   B
BROOKLYN, NY 11237 Community Board:   301
DOB Cross Street(s):   MESEROLE STREET,    SCHOLES STREET
Status:   C - JOB IS SIGNED OFF 05/12/2009
Request Type:   A - APPLICATION eFiled:   YES Permit Issued:  11/11/2008 7:18 PM
Application Entered:   11/11/2008 Job Start Date:   11/11/2008
Last Change:   05/12/2009 Job End Date:   02/11/2009
Appointment Status:   
Last Inspection By:   COHN, MARTIN       On     05/06/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011422 Licensee Name: MICHAEL RIGLIETTI
Firm: 003360 Firm Name: MSR ELECTRICAL CONST CORP
Firm Phone: 718-743-2742  Firm Address: 2737 OCEAN AVENUE BROOKLYN NY 11229 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
6 - GENERAL WIRING
Total Fee:  $201.00
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   G - Garage
Special Cert Approval:  
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: CARLO CASALINO
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   No
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  0  
B. 101 Up to 200 AMPS  2  200 AMP
C. 201 Up to 600 AMPS  0  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  0  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  2  3/0
D. Over 250 MCM  0  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  0  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  0  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
001    18  26         
Buildings Total 18  26                
Total Units : 54 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 0 #4-Wire 2 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 11/11/2008 Notice: 1 - FIRST NOTICE 04/13/2009
Power Issued: 11/11/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B310768
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 04/09/2009 04/13/2009 JMZ A E (45) (12) Y
INSPECTION COMMENTS: N
 
(2) 05/06/2009 05/12/2009 MC2 C R E (5) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B310768
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
WATER GROUND RACEWAY NOT CONTINUOUS
RSLV 04/09/2009 04/09/2009 05/06/2009
 
002 (999) OTHER
SERVICE SWITCH NOT GOURNDED
RSLV 04/09/2009 04/09/2009 05/06/2009
 
003 (999) OTHER
CHARGER IN FRONT PANEL
RSLV 04/09/2009 04/09/2009 05/06/2009
 
004 ( 15) FLEXIBLE CORDS USED AS PERMANENT WIRING METHOD
CHARGER FEED FLEX CORD
RSLV 04/09/2009 04/09/2009 05/06/2009
 
005 ( 14) CIRCUIT OVERCURRENT PROTECTION DEVICE IS OF IMPROPER SIZE
CHARGER OVER CURRENT
RSLV 04/09/2009 04/09/2009 05/06/2009
 
006 ( 19) DEFECTIVE WIRING IS IN USE
DEFECTIVE WIRING PANEL NEUTRAL BONDED
RSLV 04/09/2009 04/09/2009 05/06/2009
 
007 ( 40) LOCKNUTS ARE MISSING OR LOOSE
SERVICE RACEWAY BONDING LOCK NUTS LOOSE
RSLV 04/09/2009 04/09/2009 05/06/2009
 
008 ( 37) MOTOR DISCONNECT SWITCH HAS NOT BEEN PROVIDED
A/C NO DISCONNECT SWITCH
RSLV 04/09/2009 04/09/2009 05/06/2009
 
009 ( 56) ELECTRICAL MATERIAL USED IS NOT SUITABLE FOR THE PURPOSE INTENDED
A/C WIRING NOT APPROVED RX
RSLV 04/09/2009 04/09/2009 05/06/2009
 
010 ( 46) PANEL HAS NOT BEEN PROVIDED WITH A DIRECTORY
NO PANEL DIRECTORY
RSLV 04/09/2009 04/09/2009 05/06/2009
 
011 ( 29) OUTLET BOXES ARE NOT COVERED
PANEL TRIM MISSING
RSLV 04/09/2009 04/09/2009 05/06/2009
 
012 ( 29) OUTLET BOXES ARE NOT COVERED
RECEPTACLE COVER MISSING
RSLV 04/09/2009 04/09/2009 05/06/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.


BIS Menu  |  Applications  |  Electrical Inspection Work Order  |  Back