BIS Menu  |  Electrical Applications  |  Electrical Inspection Work Order  |  Back   FAQs  |  Glossary   
DOB Logo - Link to Homepage NYC.gov Logo - Link to Homepage
NYC Department of Buildings
Electrical Application Details for App #: B306651
Premises: 533 OCEAN AVENUE BROOKLYN BIN: 3117155     Block: 5101   Lot: 93
   
Application Completed and Certified

Filed: 533 OCEAN AV Census Tract:   510 Health Area:  7210
NONE Admin Area:   B - BROOKLYN Inspection Area:   K
BROOKLYN, NY 11226 Community Board:   314
DOB Cross Street(s):   CHURCH AVENUE,    TENNIS COURT
Status:   C - JOB IS SIGNED OFF 05/13/2009
Request Type:   A - APPLICATION eFiled:   NO
Application Entered:   07/16/2008 Job Start Date:   07/20/2008
Last Change:   05/13/2009 Job End Date:   10/20/2008
Appointment Status:   
Last Inspection By:   DOYLEY, DEXTER       On     04/29/2009      
Field Disp:   C - INSPECTION PASSED
Energize Recommendation:  E - ISSUE POWER AUTH
Objection Disposition:  R - REMOVED

License #: 011129 Licensee Name: JESUS M CORPORAN
Firm: 002506 Firm Name: JECO ELEC'L SERVICE CORP.
Firm Phone: 718-542-1931  Firm Address: 1162 INTERVALE AVENUE BRONX NY 10459 

Work Started or Filed by Others: NO
Work Category:   R - REHABILITATION Work To Be Done:  
1 - SERVICE WORK/NOTIFY UTILITY
Total Fee:  $1,419.50
Other Work:   
Work Related to a New or Amended Certificate of Occupancy:   NO
This Job Regulated by the NYC Energy Conservation Code:  
Building Used As:   Z - Commercial/Residential (36  Stores, 2 Apartments)
Special Cert Approval:   A - ADEQUATE WIRING PROGRAM
Advisory Board Approval:   NOT APPLICABLE
Owner / Occup: DOV SANDVERA
Owner Business Name: E 9 JERYG MANAGEMENT CORP
Authorized Representative:   
Relationship To Owner:   


WORK DESCRIPTION
BUILDING OVERVIEW Are Feeders Being Installed? :   Yes
(If feeders are being installed, provide a wiring diagram and calculations at the time of inspection)
Building Overview Work Items QUANTITY DESCRIPTION
SERVICE SWITCHES  
A. Up to 100 AMPS  3  
B. 101 Up to 200 AMPS  0  
C. 201 Up to 600 AMPS  1  
D. 601 Up to 1200 AMPS  0  
E. Over 1200 AMPS  0  
SER. ENT. & FDR COND (EACH SET)  
A. Up to #2 CONDUCTOR  38  
B. Over #2 to 1/0  0  
C. Over 1/0 to 250 MCM  0  
D. Over 250 MCM  1  
PANELS  
A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs  36  
B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs  0  
C. 3 Phase Up to 225 AMPS  1  
D. 3 Phase Over 225 AMPS  0  
ELEVATORS / ESCALATORS / MATERIAL LIFTS  
A. Total No. of Elevators / Escalators / Material Lifts  0  
B. Each Additional 10 Floors Or Less  0  
BOILER CONTROLS  0  

FLOOR DESCRIPTIONS
Floor Apt. Number Of Outlets No. Of
Fixtures
Motors / Generators Heaters Transformers
Fixt Receptacles Switch Num Total HP KW Num Total KW Num Total KVA
ATT A/C
Buildings Total   72                      
Total Units : 72 units   

Signs: Field Connect: 0 Field Inspect: 0 Tags:

SERVICE / METER EQUIPMENT
Meter Request to Utility #3-Wire 36 #4-Wire 3 #10-Wire 0
Existing Meters 0 + New Meters 0 - Removed Meters 0 = Total Meters 0

Power Auth Flag: I - ISSUED Objection Flag:
Power Requested: 07/16/2008 Notice: 1 - FIRST NOTICE 03/26/2009
Power Issued: 07/16/2008 Response:  

Follow-Up: K - (CLOSED)
Contractor's Comments:  

 
Inspection Details
 

INSPECTION FOR APPLICATION #: B306651
INSP
ID
FIELD
DATE
DISP
DATE
INSP
ID
FLD
DISP
OBJ
DISP
ENRG
REC
TIME
INSP
REINSP
DATE
NEW
OBJ
APPT
FLAG
 
(1) 03/17/2009 03/26/2009 DEX A E (60) (4) Y
INSPECTION COMMENTS: N
 
(2) 04/29/2009 05/04/2009 DEX C R E (40) (0) Y
INSPECTION COMMENTS: N

OBJECTION FOR APPLICATION #: B306651
OBJECTION ID OBJECTION CODE OBJECTION DESCRIPTION & COMMENTS STAT FIRST LATEST RESLVD
 
001 ( 29) OUTLET BOXES ARE NOT COVERED
SPLICE BOX IN ALL APTS MISSING COVERS THROUGOUT
RSLV 03/17/2009 03/17/2009 04/29/2009
 
002 ( 5) SERVICE GROUNDING CONDUCTOR HAS NOT BEEN INSTALLED PROPERLY
GROUND UNDERSIZED FOR 500 MCM WIRE
RSLV 03/17/2009 03/17/2009 04/29/2009
 
003 (999) OTHER
HCM PANEL NO BOLT DOWN BREAKER INSTALLED FOR SERVICE SWITCH 408.16F
RSLV 03/17/2009 03/17/2009 04/29/2009
 
004 ( 22) FIXED EQUIPMENT IS NOT PROPERLY GROUNDED
CONDUIT IN SPLICE BOXES THROUGHOUT
RSLV 03/17/2009 03/17/2009 04/29/2009



If you have any questions please review these Frequently Asked Questions, the Glossary, or call the 311 Citizen Service Center by dialing 311 or (212) NEW YORK outside of New York City.