| BUILDING OVERVIEW |
Are Feeders Being Installed? : Yes |
| (If feeders are being installed, provide a wiring diagram and calculations at the time of inspection) |
| Building Overview Work Items |
QUANTITY |
DESCRIPTION |
| SERVICE SWITCHES |
|
| A. Up to 100 AMPS |
0 |
|
| B. 101 Up to 200 AMPS |
1 |
|
| C. 201 Up to 600 AMPS |
0 |
|
| D. 601 Up to 1200 AMPS |
0 |
|
| E. Over 1200 AMPS |
0 |
|
| SER. ENT. & FDR COND (EACH SET) |
|
| A. Up to #2 CONDUCTOR |
3 |
1- SET OF 3 # 2 WIRES |
| B. Over #2 to 1/0 |
0 |
|
| C. Over 1/0 to 250 MCM |
1 |
|
| D. Over 250 MCM |
0 |
|
| PANELS |
|
| A. 1 Phase Up to 20-1 or 10-2 Pole Brkrs |
3 |
3- 100AMPS 20 CIRCUITS |
| B. 1 Phase Over to 21-1 or 10-2 Pole Brkrs |
0 |
|
| C. 3 Phase Up to 225 AMPS |
0 |
|
| D. 3 Phase Over 225 AMPS |
0 |
|
| ELEVATORS / ESCALATORS / MATERIAL LIFTS |
|
| A. Total No. of Elevators / Escalators / Material Lifts |
0 |
|
| B. Each Additional 10 Floors Or Less |
0 |
|
| BOILER CONTROLS |
0 |
|
| OBJECTION ID |
OBJECTION CODE |
OBJECTION DESCRIPTION & COMMENTS |
STAT |
FIRST |
LATEST |
RESLVD |
| |
| 001 |
( 59) |
AFCI PROTECTION HAS NOT BEEN PROVIDED APT 1 BEDROOM 210.12B |
RSLV |
09/08/2008 |
09/08/2008 |
11/24/2008 |
| |
| 002 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER APT 3 KITCHEN COUNTER 210.52 |
RSLV |
09/08/2008 |
09/08/2008 |
11/24/2008 |
| |
| 003 |
(999) |
OTHER APT 3 KITCHEN RECPT OUTLET OVER STOVE NOT PROTECTED FROM PHYSICALDAMAGE 110.2 |
RSLV |
09/08/2008 |
09/08/2008 |
11/24/2008 |
| |
| 004 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER APT 2 KITCHEN COUNTER 210.52 |
RSLV |
09/08/2008 |
09/08/2008 |
11/24/2008 |
| |
| 005 |
( 63) |
RECEPTACLE OUTLETS NOT IN SUFFICIENT NUMBER 1ST FLOOR APT 1,2,3, FEEDER UNDERSIZE 215.2 |
RSLV |
09/08/2008 |
09/08/2008 |
11/24/2008 |
| |
| 006 |
( 10) |
BRANCH CIRCUIT CONDUCTORS ARE NOT PROPER SIZE 1ST FLOOR APT BRANCH CIRCUITS TO ELECT STOVE UNDERSIZE FOR 50A LOAD210.9 |
RSLV |
09/08/2008 |
09/08/2008 |
11/24/2008 |
| |
| 007 |
( 6) |
FEEDER DIAGRAM DID NOT ACCOMPANY APPLICATION FOR INSPECTION BLDG FEEDER DIAGRAM AND APT LOAD CALCULATION OF SERVICE TO FEED SAMEHAS NOT BEEN PROVIDED TOTAL LOADS 215.5 |
RSLV |
09/08/2008 |
09/08/2008 |
11/24/2008 |